| Date |
Text |
| 2004-12-13 00:00:00 | DENIED: |
| | 1.PLEASE CLARIFY ACCESS TO NEW |
| | CONDENSER UNIT LOCATED ON THE ROOF.PER |
| | 2001 FBC(M)306.5, EQUIPMENT LOCATED ON |
| | ROOF REQUIRING ACCESS AT A HEIGHT |
| | EXCEEDING 16 FT SHALL HAVE A PERMENANT |
| | MEANS OF ACCESS.SUCH ACCESS SHALL NOT |
| | REQUIRE CLIMBING OVER OBSTRUCTIONS |
| | GREATER THAN 30 INCHES. |
| | |
| | 2.PLAN SHEET ME-1 INDICATES CONDENSING |
| | UNIT INSTALLED ON A FACTORY CURB. |
| | PLEASE PROVIDE PRODUCT APPROVAL. |
| | INDICATE HEIGHT OF CURB.PER 2001 FBC |
| | 1511.7, ROOF CURBS SHALL BE A MINIMUM OF |
| | 8" ABOVE THE ROOF SURFACE.WHERE |
| | ROOFING MATERIALS EXTEND BENEATH THE |
| | UNIT, SUPPORTS SHALL COMPLY WITH TABLE |
| | 1511.7 OF THE 2001 FBC. |
| | |
| | 3.PROVIDE INFORMATION ON THE |
| | TERMINATION OF THE CONDENSATE.SHOW |
| | COMPLIANCE WITH 2001 FBC(M)307.2.1 #2. |
| | PLEASE NOTE, CONDENSATE SHALL TERMINATE |
| | A MINIMUM OF 12 INCHES FROM THE BUILDING |
| | STRUCTURE - 2001 FBC 1503.4. |
| | |
| | 4.PLAN INDICATES A DUCT SMOKE |
| | DETECTOR.FAN SHUTDOWN BY DUCT SMOKE |
| | DETECTOR IS REQUIRED TO HAVE |
| | NOTIFICATION TO ALARM/STROBE IN NORMALLY |
| | OCCUPIED AREAS - 2001 FBC(M)606.4.1 |
| | EXCEPTION #2. |
| | |
| | 5.PLAN INDICATES O.A. OPENING AND DOES |
| | NOT INDICATE DUCTWORK.DETAIL SHOWS |
| | O.A. DUCTED TO THE R/A PLENUM AT THE AHU |
| | WHICH IS PROPER.PLEASE CLARIFY. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |