Plan Review Notes
Plan Review Notes For Permit 04110775
Permit Number 04110775
Review Stop M
Sequence Number 1
Notes
Date Text
2004-12-13 00:00:00DENIED:
 1.PLEASE CLARIFY ACCESS TO NEW
 CONDENSER UNIT LOCATED ON THE ROOF.PER
 2001 FBC(M)306.5, EQUIPMENT LOCATED ON
 ROOF REQUIRING ACCESS AT A HEIGHT
 EXCEEDING 16 FT SHALL HAVE A PERMENANT
 MEANS OF ACCESS.SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES.
  
 2.PLAN SHEET ME-1 INDICATES CONDENSING
 UNIT INSTALLED ON A FACTORY CURB.
 PLEASE PROVIDE PRODUCT APPROVAL.
 INDICATE HEIGHT OF CURB.PER 2001 FBC
 1511.7, ROOF CURBS SHALL BE A MINIMUM OF
 8" ABOVE THE ROOF SURFACE.WHERE
 ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, SUPPORTS SHALL COMPLY WITH TABLE
 1511.7 OF THE 2001 FBC.
  
 3.PROVIDE INFORMATION ON THE
 TERMINATION OF THE CONDENSATE.SHOW
 COMPLIANCE WITH 2001 FBC(M)307.2.1 #2.
 PLEASE NOTE, CONDENSATE SHALL TERMINATE
 A MINIMUM OF 12 INCHES FROM THE BUILDING
 STRUCTURE - 2001 FBC 1503.4.
  
 4.PLAN INDICATES A DUCT SMOKE
 DETECTOR.FAN SHUTDOWN BY DUCT SMOKE
 DETECTOR IS REQUIRED TO HAVE
 NOTIFICATION TO ALARM/STROBE IN NORMALLY
 OCCUPIED AREAS - 2001 FBC(M)606.4.1
 EXCEPTION #2.
  
 5.PLAN INDICATES O.A. OPENING AND DOES
 NOT INDICATE DUCTWORK.DETAIL SHOWS
 O.A. DUCTED TO THE R/A PLENUM AT THE AHU
 WHICH IS PROPER.PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  