| 2004-12-03 00:00:00 | *************** UNSAT ************** |
| | |
| | |
| | 1)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | PLEASE SEE LOADS SHOWN DO NOT SEE TO ADD |
| | UP TO THE AMOUNTS SHOWN. |
| | |
| | 2)NOTE: PLEASE SEE 424.3B FOR A/C OCP. |
| | THE AMPACITY OF THE BRANCH-CIRCUIT |
| | CONDUCTORS AND THE RATING OR SETTING OF |
| | OVERCURRENT PROTECTIVE DEVICES SUPPLYING |
| | FIXED ELECTRIC SPACE-HEATING EQUIPMENT |
| | CONSISTING OF RESISTANCE ELEMENTS WITH |
| | OR WITHOUT A MOTOR SHALL NOT BE LESS |
| | THAN 125 PERCENT OF THE TOTAL LOAD OF |
| | THE MOTORS AND THE HEATERS. THE RATING |
| | OR SETTING OF OVERCURRENT PROTECTIVE |
| | DEVICES SHALL BE PERMITTED IN ACCORDANCE |
| | WITH 240.4(B). A CONTACTOR, THERMOSTAT, |
| | RELAY, OR SIMILAR DEVICE, LISTED FOR |
| | CONTINUOUS OPERATION AT 100 PERCENT OF |
| | ITS RATING, SHALL BE PERMITTED TO SUPPLY |
| | ITS FULL-RATED LOAD AS PROVIDED IN |
| | 210.19(A), |
| | PLEASE SEE 20A OCP FOR 5200KVA LOAD. |
| | |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |