Plan Review Notes
Plan Review Notes For Permit 04110775
Permit Number 04110775
Review Stop B
Sequence Number 1
Notes
Date Text
2004-12-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110775
 ADD: 501 S OLIVE AV
 CONT: NICK RAICH
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) PROVIDE MINIMUM BLDG TYPE SEE TABLE
 600. ALSO SEE 705.1.1.2 EVERY WALL
 WITHIN 15' OF A PROPERTY LINE SHALL BE
 EQUIPPED WITH OPENING PROTECTIVES. SEE
 EXCEPTION FOR SHOW WINDOWS, ARE THESSE
 TO BE SHOW WINDOWS?
  
 2) 2304.1.2. SOIL TREATMENT FOR TERMITES
 OR OTHER ALTERNATIVES.
 PROVIDE INFORMATION
  
 3)SEE S-1 EXTERIOR WALL SECTION IS
 MISSSING BLOCK WALL RECESS: 2111.1.9
 1 1/2" RECESS WATERSTOP FOR EXTERIOR
 WALLS.
  
 4) S-1 MISSING THE MANSARD ROOF TRUSS
 FRAMING INFORMATION, TIE DOWN,
 MANUFACTURER OF TIE DOWN, MODEL #, LOADS
 TO BE IMPOSED ETC...
  
 5)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) STORM SHUTTERS
 C) SOFFITS
 D) COMPONENTS & CLADDING- TRUSS
 ANCHORS
 E) ROOFING ASSEMBLIES UNDERLAYMENTS,
 & ROOF FINISHES
  
 6) 1503.4.2 OVERFLOW DRAINS SHALL BE THE
 SAME SIZE AS ROOF DRAINS, INSTALLED WITH
 THE INLET FLOW LINE LOCATED 2" ABOVE THE
 LOWEST POINT OF THE ROOF LINE. OVERFLOW
 SCUPPERS SHALL BE A MINIMUM OF 4"IN
 HEIGTH AND SHALL BE PLACED IN WALLS OR
 PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF
 SURFACE.
  
 7) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 8) 1511.7 ROOF MOUNTED MECHANICAL UNIT S
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 9)1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026