| Plan Review Notes For Permit 04110753 |
| Permit Number |
04110753 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-05-26 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | | | | 1} THE FOUR RECEPTACLES ADDED TO THE | | | EAST SIDE OF THE BUILDING DO NOT HAVE | | | PANEL DESIGNATION OR CIRCUIT NUMBER(S). | | | PLEASE ADD SAME TO PLAN. | | | | | | 2} PLEASE SHOW LOCATION OF WATER HEATER | | | DISCONNECT PER 422.30. | | | | | | 3} INDICATE THE AIC RATING OF THE | | | DISCONNECTS ADDED TO THE RISER PER | | | 110.10. | | | | | | NOTE: SEE MECHANICAL PROVISO ON SHEET | | | M-1 | | | (PRIOR REVIEW)AND INDICATE COMPLIANCE | | | WITH SAME ON APPLICABLE SHEETS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|