| Plan Review Notes For Permit 04110753 |
| Permit Number |
04110753 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-01-21 00:00:00 | PROVISO: | | | PER 2001 FBC(M)606.2.2, WHERE MULTIPLE | | | SYSTEMS A COMMON PLENUM AND THE | | | AGGREGATE CAPACITY IS GREATER THAN 2,000 | | | CFM, THE SUPPLY & RETURN AIR SYSTEM | | | SHALL HAVE A DUCT SMOKE DETECTOR. | | | | | | DUCT SMOKE DETECTOR SHALL HAVE | | | NOTIFICATION TO ALARM/STROBE IN NORMALLY | | | OCCUPIED AREAS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|