Plan Review Notes
Plan Review Notes For Permit 04110753
Permit Number 04110753
Review Stop M
Sequence Number 2
Notes
Date Text
2005-01-21 00:00:00PROVISO:
 PER 2001 FBC(M)606.2.2, WHERE MULTIPLE
 SYSTEMS A COMMON PLENUM AND THE
 AGGREGATE CAPACITY IS GREATER THAN 2,000
 CFM, THE SUPPLY & RETURN AIR SYSTEM
 SHALL HAVE A DUCT SMOKE DETECTOR.
  
 DUCT SMOKE DETECTOR SHALL HAVE
 NOTIFICATION TO ALARM/STROBE IN NORMALLY
 OCCUPIED AREAS.
  