| Plan Review Notes For Permit 04110753 |
| Permit Number |
04110753 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-08 00:00:00 | DENIED: | | | 1.FRESH AIR INTAKE TO AHU #1 & 2 IS | | | LOCATED WITH IN 10 FT OF THE TOILET | | | EXHAUST.FRESH AIR INTAKE SHALL BE | | | LOCATED AS NOT TO RECIRCULATE EXHAUST | | | AIR PER 2001 FBC(M)501.3. | | | | | | 2.PLAN SHEET M-1 DETAIL FOR THE | | | SUSPENDED AHU SHOWS A SAFE PAN WITH A | | | DRAIN.PLEASE INDICATE THE TERMINATION | | | POINT OF THE AUXILIARY DRAIN LINE.PER | | | 2001 FBC(M)307.2.3, THE AUXILIARY DRAIN | | | SHALL TERMINATE AT A CONSPICUOUS POINT | | | TO SERVE AS AN ALARM. | | | | | | 3.PLAN SHEET ME-1 THE EQUIPMENT STAND | | | DETAIL INDICATES 18" FOR THE HEIGHT. | | | PLEASE SEE THE ATTACHED SCHEDULE FOR THE | | | MINIMUM CLEARANCE BETWEEN THE ROOF | | | SURFACE AND THE BOTTOM OF THE SUPPORT | | | RAIL. | | | | | | 4.PLEASE CLARIFY IF THE TENANT | | | IMPROVEMENT IS FOR A NEW TENANT OR | | | EXISTING TENANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|