Plan Review Notes
Plan Review Notes For Permit 04110753
Permit Number 04110753
Review Stop M
Sequence Number 1
Notes
Date Text
2004-12-08 00:00:00DENIED:
 1.FRESH AIR INTAKE TO AHU #1 & 2 IS
 LOCATED WITH IN 10 FT OF THE TOILET
 EXHAUST.FRESH AIR INTAKE SHALL BE
 LOCATED AS NOT TO RECIRCULATE EXHAUST
 AIR PER 2001 FBC(M)501.3.
  
 2.PLAN SHEET M-1 DETAIL FOR THE
 SUSPENDED AHU SHOWS A SAFE PAN WITH A
 DRAIN.PLEASE INDICATE THE TERMINATION
 POINT OF THE AUXILIARY DRAIN LINE.PER
 2001 FBC(M)307.2.3, THE AUXILIARY DRAIN
 SHALL TERMINATE AT A CONSPICUOUS POINT
 TO SERVE AS AN ALARM.
  
 3.PLAN SHEET ME-1 THE EQUIPMENT STAND
 DETAIL INDICATES 18" FOR THE HEIGHT.
 PLEASE SEE THE ATTACHED SCHEDULE FOR THE
 MINIMUM CLEARANCE BETWEEN THE ROOF
 SURFACE AND THE BOTTOM OF THE SUPPORT
 RAIL.
  
 4.PLEASE CLARIFY IF THE TENANT
 IMPROVEMENT IS FOR A NEW TENANT OR
 EXISTING TENANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  