Plan Review Notes
Plan Review Notes For Permit 04110753
Permit Number 04110753
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-24 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE RISER APPEARS TO BE
 INCOMPLETE AT THIS TIME?
 PLEASE SEE ONCE POWER COMES TO NEW 400A
 METER BANK SHOWN, NO ADDITIONAL
 INFORMATION IS SHOWN FOR MAINS, OCP,
 CONDUITS, FEEDERS, EQUIPMENT
 GROUNDING?ETC.
 215.5,310.16,240.4,250.110,.250.122,ETC.
 15.5,310.16,240.4,250.110,.250.122,ETC.
  
 PLEASE SEE ONE SET OF PLANS IS REDLINED
 FOR AREA OF CONCERN.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE BE SURE ALL OLD/VOIDED SHEETS ARE
 REMOVED FROM SETS AND ONLY NEW REVISED
 SHEETS ARE INSERTED INTO COMPLETE SETS.
 ONE SET/COPY OF OLD SHEETS SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE ONLY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  