| Plan Review Notes For Permit 04110666 |
| Permit Number |
04110666 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | | | | 1) SHT A-3 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. ONLY THE | | | FIXTURES WITHIN THE BATHROOMGROUP SHALL | | | CONNECT TO THE WET-VENTED HORIZONTAL | | | BRANCH DRAIN. ANY ADDITIONAL FIXTURES | | | SHALL DISCHARGE DOWNSTREAM OF THE WET | | | VENT. SECTION 909.1. (THE KITCHEN SINK | | | SHALL CONNECT DOWNSTREAM OF THE BATHROOM | | | FIXTURES) - SEE RED LINE CORRECTIONS FOR | | | AN EXAMPLE OF HOW THE RISER WILL MEET | | | CODE REQUIREMENTS. | | | 2) ALL DRAWINGS SHALL BEAR THE NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN. SECTION 104.2.1 - STAMPED | | | SIGNATURES ARE NOT APPROVED. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|