Plan Review Notes
Plan Review Notes For Permit 04110666
Permit Number 04110666
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1) SHT A-3 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. ONLY THE
 FIXTURES WITHIN THE BATHROOMGROUP SHALL
 CONNECT TO THE WET-VENTED HORIZONTAL
 BRANCH DRAIN. ANY ADDITIONAL FIXTURES
 SHALL DISCHARGE DOWNSTREAM OF THE WET
 VENT. SECTION 909.1. (THE KITCHEN SINK
 SHALL CONNECT DOWNSTREAM OF THE BATHROOM
 FIXTURES) - SEE RED LINE CORRECTIONS FOR
 AN EXAMPLE OF HOW THE RISER WILL MEET
 CODE REQUIREMENTS.
 2) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. SECTION 104.2.1 - STAMPED
 SIGNATURES ARE NOT APPROVED.
  
  
 REVIEW BY KEN STEVENS