| Notes |
| Date |
Text |
| 2004-11-22 00:00:00 | *** UNSAT *** | | | | | | 1)NOTE: PLEASE PROVIDE CIRCUITING ON | | | PLANS AND CORRELATE WITH A PANEL | | | SCHEDULE FOR EACH UNIT. | | | NEW PANEL/ EXSITING? | | | PLEASE ALSO PROVIDE SIZE OF EACH AND | | | LOAD. | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE 220.12B FOR TRACK | | | LT-ING LOADS. | | | PLEASE SEE ALL CONTINUOS LOADS ARE TO BE | | | SHOWN AT 125%. | | | 215.3,230.42 ETC. | | | | | | 3)NOTE: PLEASE CLARIFY OF THERE ARE ANY | | | NEW OR EXISTING EXIT/EM LTS? | | | PLEASE ALSO SEE 700.12E FOR CIRCUITINGIF | | | TO BE NEW? | | | | | | 4)NOTE: PLEASE VERIFY IF NEW OR EXISTING | | | SIGN CIRCUIT PER 600.5? | | | | | | 5)NOTE: PLEASE SEE FBC 104.2.1 WHICH | | | REQUIRES A PRINTED NAME AND SIGNATAURE | | | FOR PERSON RESPONSIBLE FOR PLANS. | | | | | | 6)NOTE: PLEASE PROVIDE COPY OF CONTRACT | | | TO VERUFY VALUE. 104.6.5 FBC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATIONFOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|