Text |
| 2005-05-02 00:00:00 | ********* UNSAT ********** |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER AND PANEL |
| | SCHEDULES SUBMITTED. |
| | RISER SHOWS "NEW" METER/MAIN FEED TO |
| | CABCANA PANEL? |
| | |
| | 2)NOTE: PLEASE SEE SECOND FLR PANEL |
| | SHOWS A MCB , YET ALSO SHOWS |
| | BACK-FEEDING A 2P-60A FOR MAIN? |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE PANEL SCHEDULE IN |
| | CABANA SHOWS A LAUNDRY CIRCUIT AND |
| | WASHER CIRCUIT, LOAD CALCS SHOWS ONLY A |
| | LAUNDRY CIRCUIT. |
| | PLEASE CORRELATE 215.5 |
| | |
| | 4)NOTE: PLEASE VERIFY ALL WATER HEATER |
| | LOADS AND OCP. |
| | PLEASE SEE LOAD CALCS INDICATE 16KW ? |
| | PLEASE SEE CABANA PANEL NOW INDICATES |
| | 2-2POLE 60A CIRCUITS ?? |
| | PLEASE CORRELATE. |
| | |
| | 5)NOTE: PLEASE CORRELATE AHU/ HEAT |
| | LOADS, OCP, AWG. |
| | PLEASE SEE LOAD CALCS AND PANEL |
| | SCHEDULES. |
| | |
| | 6)NOTE: PLEASE PROVIDE LOAD CALCS FOR |
| | CABANA PANEL. |
| | PLEASE ADJUST LOAD CALCS FOR METER/MAIN |
| | AFTER CORRECTIONS. |
| | 215.5,220.31/31B |
| | |
| | 7)NOTE: PLEASE SEE POOL PUMP INDICATES |
| | BEING 220V AND YET SHOWN AS 1-POLE? |
| | |
| | 8)NOTE: PLEASE SEE ALL REVISIONS TO |
| | PLANS MUST BE CLOUDED AND TRIANGLED AND |
| | CORRELATE WITH TITLE BLOCK FOR REV'S AND |
| | DATES. |
| | PLEASE SEE SOME ITEMS HAVE CHANGED FROM |
| | ORIGINAL PLANS YET, THESE DO NOT SEEM TO |
| | BE CLOUDED. |
| | |
| | NEW COMMENT |
| | |
| | 1)NOTE: PLEASE SEE A MAIN/DISCONNECTING |
| | MEANS FOR EXISTING CABANA PANELIS |
| | REQUIRED. THIS WAS MISSED ON ORIG |
| | REVIEW. |
| | PLEASE SEE 225.31-225.36 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |