| 2004-11-19 00:00:00 | ******** UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE PLANS INDICATE A NEW |
| | 200A SERVICE TO BE INSTALLED, HOWEVER A |
| | NEW RISER DIAGRAM WAS NOT SUBMITTED FOR |
| | REVIEW? PANEL SCHEDULE? |
| | 215.5 |
| | PLEASE ALSO SEE THERE IS NO INFORMATION |
| | FOR CABANA? HOW IS THIS FED? EXISTING? |
| | PLEASE SUBMIT A COMPLETE RISER DIAGRAM |
| | SHOWING NEW AND/OR ANY EXISTING? |
| | PLEASE INCLUDE SEC'S FEEDERS, DISC FOR |
| | DEATCHED BLDG, GROUNDING ELECTRODE |
| | SYSTEM FOR BOTH BLDGS. ETC |
| | 250.50,250.32,225.31,310.15B6,110.9 |
| | |
| | |
| | 2)NOTE:PLEASE SUBMIT LOAD CALCULATIONS |
| | FOR NEW LOADS ADDED. CENTRAL A/C? |
| | WASHER? |
| | |
| | 3)NOTE: PLEASE LABEL RMS ON PLANS, ALONG |
| | WITH FIRST AND SECONDFLOORS/CABANA |
| | IDENTIFICATION. |
| | |
| | 3)NOTE: PLEASE SEE A SD WILL BE REQUIRED |
| | INSIDE CABANA. NFPA-72 |
| | |
| | 4)NOTE: PLEASE SEE 210.52C1 FOR RECEPT |
| | SPACING IN KITCHEN. (MISSING ONE, SEE |
| | REDLINE ON ONE SET. |
| | |
| | 5)NOTE: PLEASE CLARIFY NEW AREA |
| | DOWNSTAIRS, IS THIS ALREADY CLOSED IN? |
| | EXISTING ELECTRICAL? IF NEW, PROVIDE |
| | OUTLETS PER 210.52 |
| | |
| | |
| | 6) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 7)NOTE: PLEASE SEE ARC FAULT TO BE |
| | REQUIRED FOR NEW ELECTRICAL IN BEDRM |
| | AREAS AND ADAPTABLE SLEEPING AREA OF |
| | CABANA. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. PLEASE DO NOT HESITATE TO CALL |
| | IF THERE ARE ANY QUESTIONS OR FOR ANY |
| | CLARIFICATION OF QUESTIONS ABOVE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |