Plan Review Notes
Plan Review Notes For Permit 04110639
Permit Number 04110639
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-27 00:00:00DENIED
 REFERENCE; FBC-2001 424.2 SWIMMING
 POOLS
  
 A) THE FOLLOWING INFORMATION REQUIRED
 ON
 THE PLANS FOR POOL PERMIT. PLEASE
 SUBMIT
 A DETAIL, MANUF SPECIFICATION SHEETS,
 OR
 ADD INFORMATION TO NOTES OF PLANS AS
 REQUIRED.
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. (ADD TO NOTES)
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 3) FBC-2001 424.2.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK. (DETAIL)
 4) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2938-95, BACKFLOW REQUIRED ON THE
 WATER SERVICE. (ADD TO NOTES)
 5) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 6) FBC-2001 424.2.13.2 JOINTS AND
 CONNECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING AND
 FITTINGS. (ADD TO NOTES)
 7) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. AQUACAL HEAT PUMP DOES NOT SHOW
 THIS REQUIREMENT INTERNALLY, SO AN
 EXTERNAL HARTFORD LOOP WILL BE REQUIRED.
 INDICATE THIS ON THE POOL EQUIPMENT
 DIAGRAM SHEET 2 OF 4.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]