| 2004-11-23 00:00:00 | ******* UNSAT ******* | | | | | | 1)NOTE: PLEASE SUBMIT COMPLETE LOAD | | | CALCULATIONS SHOWING ALL EXISTING AND | | | NEW LOADS. 220.31B | | | PLEASE BE SURE ALL LARGEST MOTORS AND | | | CONTINUOUS LOADS ARE SHOWN AT | | | 125%.(HEAT-PUMP) | | | 215.3,230.42 ETC | | | | | | 2)NOTE: PLEASE INDICATE FEED FOR NEW | | | PANEL SHWON ON DIAGRAM. PLEASE SHOW OCP | | | FOR FEED, CONDUIT, CONDUCTOR SIZES ETC. | | | | | | 3)NOTE: PLEASE SEE FBC 104.2.1 FOR ALL | | | PLANS/DEATILS SUBMITTED. | | | | | | PLEASE ALSO SEE FS 471.025, FOR PLANS | | | WHICH CONTAIN A TITLE BLOCK FROM AN | | | ENGINEER, MUST ALSO BE SIGNED,DATED AND | | | SEALED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|