Plan Review Notes
Plan Review Notes For Permit 04110624
Permit Number 04110624
Review Stop M
Sequence Number 5
Notes
Date Text
2006-04-27 00:00:00*** DENIED ***
 1) DUCTS GOING THRU THE FIRE RATED WALL
 IN THE FILE STOR. ROOM MUST BE METAL
 WITH FIRE DAMPERS, PER 2004 FBC/M
 607.5.3 SEE ATTACHED A-2 .
  
 2) DUCTS GOING THRU THE FIRE RATED WALL
 FROM LIVING ROOM #3 TO DINING ROOM MUST
 BE METAL WITH FIRE DAMPERS, SEE ATTACHED
 A-3 .
  
 3) PLEASE EXPLAIN RETURN AIR FOR GROUND
 FLOOR PG. M-2AHU #1 & # OVER BATHROOMS
 IS THAT TO BE A ENCLOSED WALL AROUND FOR
 A PLENUM OR IS THE ENTIRE FIRST FLOOR
 ATTIC THE PLENUM.
  
 4) PAGE M-2 GROUND FLOOR, MOST RETURN
 AIR TRANSFER DUCTS ARE UNDRE SIZED, SEE
 NOTE #5(A).
  
 5) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  