Notes
Date Text
2005-08-01 00:00:00PASSED/PROVISO
  
 3/4" REQUIRED TO EACH HEATER.
 AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE.
 A FULL OPEN VALVE IS REQUIRED ON THE
 WATER DISTRIBUTION SUPPLY PIPE AT THE
 ENTRANCE TO THE STRUCTURE.
 SECOND FLOOR WATER RISER SHALL BE
 UPSTREAM OF VALVE TO WATER HEATER FIRST
 FLOOR.
 A FULL OPEN VALVE IS REQUIRED ON THE
 ENTRANCE TO EVERY WATER SUPPLY PIPE TO
 EVERY DWELLING UNIT & ON THE WATER
 SUPPLY PIPE TO EVERY WATER HEATER.
 606.1(5) & (7).
 A FULL OPEN VALVE IS REQUIRED ON THE
 BASE OF THE WATER RISER. 606.1(3).
 KITCHEN SINK HEIGHT 11-44.24.2 AND KNEE
 CLEARANCE 11-4.24.3 SHALL COMPLY.