Plan Review Notes
Plan Review Notes For Permit 04110624
Permit Number 04110624
Review Stop P
Sequence Number 3
Notes
Date Text
2005-04-27 00:00:00 
 DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FLORIDA STATUTES
  
 A) FROM PREVIOUS REVIEWS:
 1) SHT A-2 KITCHEN SINK SHALL COMPLY
 WITH SECTION 4.24 ALL ALL SUBMSECTIONS.
 PLEASE SUBMIT A DETAIL. THE FOLLOWING
 INFORMATION IS STILL REQUIRED:
 A) HEIGHT 11-4.24.2
 B) CLEAR FLOOR SPACE 11-4.24.5 SHALL BE
 PROVIDED TO ALLOW FORWARD APPROACH AND
 SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH
 THE SINK. (FIG. 32)
 C) EXPOSED PIPES & SURFACES 11-4.24.6
 D) FAUCETS 11-4.24.7
 4) SUBMIT A WATER RISER DIAGRAM REQUIRED
 BY SECTION 104.3.1.1. SHOW ALL PIPE
 SIZES.
 6) THERMAL EXPANSION CONTROL IS REQUIRED
 ON ALL WATER HEATERS. SHOW ON THE DETAIL
 FOR THE W/HEATERS. SECTION 607.3.2.
 1B) FOR ACCESSIBLE TOILET ROOMS SHOW THE
 FOLLOWING INFORMATION:
 C) FLUSH CONTROLS 11-4.16.5
 F) EXPOSED PIPES & SURFACES 11-4.19.4
 H) LAV SHALL BE SHOWN A MINIMUM 15" OFF
 THE WAALL TO THE CENTERLINE OF THE
 FIXTURE TO BE CENTERED ON THE 30" OF THE
 CLEAR FLOOR SPACE.
 ******NEW COMMENTS********
 1C) HAND DRAWN CORRECTIONS TO A SIGNED,
 SEALED & DATED SET OF PLANS IS NOT
 APPROVED UNLESS EACH CORRECTIONS IS
 SIGNED & DATED BY THE ARCHITECT OF
 RECORD. - ALSO WHITE OUT IS NOT APPROVED
 FOR CHANGES ON SIGNED/SEALED DRAWINGS.
 SECTION 104.2.1.3
 2C) SEE ELECTRICAL REVIEW COMMENT
 ADDRESSING 553.80(2)(B) AND 4 X FEE
 REQUIRED TO BE PAID PRIOR TO
 RESUBMITTING PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]