| Date |
Text |
| 2005-04-29 00:00:00 | DENIED:3RD REQUEST |
| | 1.PROVIDE DDETAIL FOR PENETRATIONS - |
| | RESPONSE IS TO REFERENCE A4 OF A5, PLAN |
| | SHEET A5 INDICATES PENETRATION FOR |
| | "CABLES" BUT NO DETAIL FOR THE FIRE |
| | DAMPERS.PLEASE NOTE FIRE DAMEPRS ARE |
| | MISSING FOR DUCTS PENETRATING RATED WALL |
| | FROM THE FILE ROOM INTO THE |
| | "MULTI-PURPOSE" ROOM.PLEASE NOTE FLEX |
| | DUCT IS PROHIBITED FROM PENETRATING A |
| | RATED WALL, 2001 FBC(M)603.5.5. |
| | |
| | 2.OUTSIDE AIR CALCULATIONS ACCORDING |
| | TO THE RESPONSE ARE NOTED ON PLAN SHEET |
| | M1.NO O.A. CALUCALTIONS INIDCATED. |
| | PROVIDE O.A. CALCS FOR THE COMMON AREAS |
| | AS WELL AS THE RESIDENCE. |
| | |
| | 4. INDICATE O.A. DUCT SIZE, MATERIAL, |
| | LAYOUT AND INTAKE. |
| | |
| | 5.RETURN AIR JUMPERS WERE NOT |
| | INCREASED TO 1 1/2 TIMES THE SQUARE |
| | INCHES OF THE SUPPLY AIR. |
| | |
| | 7.DUCT SMOKE DETECTOR IS NOT INDICATED |
| | ON THE PLAN. |
| | |
| | 8.PROVIDE SUBMITTAL FOR THE HOOD, |
| | EXHAUST SHALL NOT TERMINATE ONTO |
| | WALKWAYS.RESPONSE INDICATES |
| | TERMINATION TO EXTERIOR WALL BUT IS NOT |
| | IDENTIFIED ON THE PLAN.MECHANICAL PLAN |
| | CONFLICTS WITH THE ELECTRICAL PLAN.THE |
| | 1ST FLOOR KITCHEN AREA SHOWS A MICROWAVE |
| | OVEN ON THE ELECTRICAL PLAN & A RANGE |
| | W/HOOD ON THE MECHANICAL PLAN.PLEASE |
| | CLARIFY. |
| | |
| | 9.EQUIPMENT SCHEDULE NOT GIVEN FOR THE |
| | EXHAUST FANS. |
| | |
| | 10.LOCATION OF THE AHU ON THE FIRST |
| | FLOOR.PLEASE NOTE RETURN AIR DUCT |
| | SHALL BE DUCTED INTO THE AHU IN THIS |
| | FIRE RATED ROOM.WHY WOULD THE AHU BE |
| | LOCATED IN THE ONLY "FIRE RATED" ROOM IN |
| | THE BUILDING? |
| | |
| | 11.LINE SIZES FOR THE LIQUID, SUCTION |
| | AND CONDENSATE ARE NOT INDICATED. |
| | |
| | 12 & 13. CONDENSATE TERMINATION IS NOT |
| | INDICATED. |
| | |
| | NEW COMMENT: |
| | PLAN SHEET A-2 INDICATED BUILDING |
| | CATEGORY AS R-3. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |