| 2005-04-20 00:00:00 | ********** UNSAT 3RD REVIEW ********** |
| | |
| | PLEASE SEE COMMENTS FROM PREVIOUS TWO |
| | REVIEWS WHICH STILL NEED TO BE ADDRESSED |
| | FOR CODE COMPLIANCE. |
| | |
| | |
| | PLEASE SEE NOTES TAKEN DIRECTLY IN |
| | NUMBERED ORDER FROM PREVIOUS TWO |
| | REVIEWS. |
| | |
| | 1)NOTE: NOTE #1 OK. |
| | |
| | 2)NOTE: NOTE #2 NO. PLEASE SEE 424.3B |
| | FOR SIZING OF AHU'S, PLEASE SEE 5KW HEAT |
| | STRIPS ON 60A OCP . PLEASE ALSO SEE #8 |
| | AWG.310.16, 240.4 ETC. |
| | PLEASE SEE MORE THAN ONE AHU SHOWN FOR |
| | UNIT #2. |
| | PLEASE SEE LOAD CALCULATIONS FOR AHU'S |
| | IN UNIT #2. |
| | |
| | 3)NOTE: NOTE#3, NO. PLEASE SEE NEXT NOTE |
| | FOR LOAD CALCS. |
| | |
| | 4)NOTE: NOTE #4 NO. SEE PREVIOUS NOTES. |
| | |
| | 5)NOTE: NOTE #5 OK. |
| | |
| | 6)NOTE: NOTE #6 NO, PLEASE SEE FEEDERS |
| | FOR UNITS. PLEASE CORRELATE AND PLEASE |
| | SEE 310.16,240.4B ETC. |
| | |
| | 7)NOTE: NOTE #7 NO, PLEASE SE PLANS |
| | STILL ONLY SHOW ONE SMALL APPLIANCE. |
| | 220.16,210.1C1,210.52B1 |
| | |
| | 8)NOTE: NOTE #8 NO, SEE PREVIOUS NOTES. |
| | |
| | 9)NOTE: NOTE #9OK. |
| | |
| | 10)NOTE: NOTE #10 NO, SEE PREVIOUS |
| | NOTES. |
| | |
| | 11)NOTE: NOTE #11 NO, SEE PREVIOUS |
| | REVIEWS. |
| | |
| | 12)NOTE: NOTE #12 OK. |
| | |
| | 13)NOTE: NOTE #13 OK, ADDED NOTE. |
| | |
| | 14)NOTE: NOTE #14 NO, SEE PREVIOUS |
| | NOTES. |
| | |
| | 15)NOTE: NOTE #15 OK. |
| | |
| | 16)NOTE: NOTE #16 OK. |
| | |
| | 17)NOTE: NOTE #17 OK. |
| | |
| | 18)NOTE: NOTE #18 OK. |
| | |
| | 19)NOTE: NOTE #19 OK. |
| | |
| | 20)NOTE: NOTE #20 OK. |
| | |
| | 21)NOTE: NOTE #21 NO, PLEASE SEE A NOTE |
| | WAS ADDED FOR CLEARENCE FOR A/C DISC'S |
| | TO BE 30", HOWEVER, PLEASE SEE MIN PER |
| | 110.26. |
| | PLEASE SEE WALL ARE STILL SHOWN ON PLANS |
| | CONFINING DISC'S. |
| | |
| | ALSO NOTE FROM PREVIOUS REVIEW #2. |
| | |
| | 1)NOTE: PLEASE SEE A NOTICE WAS GIVEN |
| | WITH RESPECT TO DESIGN PROFESSIONAL AND |
| | FS 553.80(2)(B). PLEASE SEE THAT NOTICE |
| | WAS GIVEN TO NOTIFY DESIGN PROFESSIONAL |
| | IF PLANS COME BACK WITH ANY OF THE SAME |
| | COMMENTS FOR CODE COMPLIANCE NOT |
| | ADDRESSED THAT A 4X FEE FOR PLAN REVIEW |
| | PORTION OF PERMIT FEE SHALL BE ACCESSED. |
| | THIS IS A REQUIRED FEE UNDER FS AND IS |
| | NOW ACCESSED. PLEASE SEE NUMEROUS |
| | COMMENTS FROM PREVIOUS TWO REVIEWS WERE |
| | NOT ADDRESSED. |
| | PLEASE SEE A FEE OF $6792.00 HAS NOW |
| | BEEN ATTACHED AND THIS FEE MUST BE PAID |
| | BEFORE RESUBMITTING PLANS. THIS IS |
| | REQUIRED UNDER FS 553.80(2)(B). |
| | PLEASE BE AWARE THE COPY OF ABOVE FS IS |
| | ATTACHEDONCE AGAIN. |
| | |
| | **PLEASE SEE ONE SET OF THE ELECTRICAL |
| | PLANS ARE BEING RETAINED FOR FILE. |
| | PLEASE SEE THESE MAY BE SENT TO THE |
| | BOARD OF ARCH'S FOR REVIEW. |
| | |
| | 2)NOTE: PLEASE PROVIDE A COMPLETE |
| | CONTRACT SHOWING VALUATION FOR COMPLETE |
| | ELECTRICAL WORK AS SET FORTH ON PLANS. |
| | PLEASE SEE LOCAL ADMINISTRATIVE CODE/FBC |
| | 104.6.5. |
| | PLEASE SEE FS 471.003, IF VALUE FOR |
| | ELECTRICAL SCOPE OF WORK IS $50K OR |
| | MORE, PLANS WILL BE REQUIRED TO BE DONE |
| | BY A PROFESSIONAL ENGINEER. |
| | |
| | 3)NOTE: PLEASE SEE ONE SETOF PLANS |
| | HAVE MANY OF THE ABOVE REDLINED AT |
| | LOCATIONS OF COMMENTS ONCE AGAIN. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETSFOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |