Plan Review Notes
Plan Review Notes For Permit 04110624
Permit Number 04110624
Review Stop E
Sequence Number 3
Notes
Date Text
2005-04-20 00:00:00********** UNSAT 3RD REVIEW **********
  
 PLEASE SEE COMMENTS FROM PREVIOUS TWO
 REVIEWS WHICH STILL NEED TO BE ADDRESSED
 FOR CODE COMPLIANCE.
  
  
 PLEASE SEE NOTES TAKEN DIRECTLY IN
 NUMBERED ORDER FROM PREVIOUS TWO
 REVIEWS.
  
 1)NOTE: NOTE #1 OK.
  
 2)NOTE: NOTE #2 NO. PLEASE SEE 424.3B
 FOR SIZING OF AHU'S, PLEASE SEE 5KW HEAT
 STRIPS ON 60A OCP . PLEASE ALSO SEE #8
 AWG.310.16, 240.4 ETC.
 PLEASE SEE MORE THAN ONE AHU SHOWN FOR
 UNIT #2.
 PLEASE SEE LOAD CALCULATIONS FOR AHU'S
 IN UNIT #2.
  
 3)NOTE: NOTE#3, NO. PLEASE SEE NEXT NOTE
 FOR LOAD CALCS.
  
 4)NOTE: NOTE #4 NO. SEE PREVIOUS NOTES.
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE FEEDERS
 FOR UNITS. PLEASE CORRELATE AND PLEASE
 SEE 310.16,240.4B ETC.
  
 7)NOTE: NOTE #7 NO, PLEASE SE PLANS
 STILL ONLY SHOW ONE SMALL APPLIANCE.
 220.16,210.1C1,210.52B1
  
 8)NOTE: NOTE #8 NO, SEE PREVIOUS NOTES.
  
 9)NOTE: NOTE #9OK.
  
 10)NOTE: NOTE #10 NO, SEE PREVIOUS
 NOTES.
  
 11)NOTE: NOTE #11 NO, SEE PREVIOUS
 REVIEWS.
  
 12)NOTE: NOTE #12 OK.
  
 13)NOTE: NOTE #13 OK, ADDED NOTE.
  
 14)NOTE: NOTE #14 NO, SEE PREVIOUS
 NOTES.
  
 15)NOTE: NOTE #15 OK.
  
 16)NOTE: NOTE #16 OK.
  
 17)NOTE: NOTE #17 OK.
  
 18)NOTE: NOTE #18 OK.
  
 19)NOTE: NOTE #19 OK.
  
 20)NOTE: NOTE #20 OK.
  
 21)NOTE: NOTE #21 NO, PLEASE SEE A NOTE
 WAS ADDED FOR CLEARENCE FOR A/C DISC'S
 TO BE 30", HOWEVER, PLEASE SEE MIN PER
 110.26.
 PLEASE SEE WALL ARE STILL SHOWN ON PLANS
 CONFINING DISC'S.
  
 ALSO NOTE FROM PREVIOUS REVIEW #2.
  
 1)NOTE: PLEASE SEE A NOTICE WAS GIVEN
 WITH RESPECT TO DESIGN PROFESSIONAL AND
 FS 553.80(2)(B). PLEASE SEE THAT NOTICE
 WAS GIVEN TO NOTIFY DESIGN PROFESSIONAL
 IF PLANS COME BACK WITH ANY OF THE SAME
 COMMENTS FOR CODE COMPLIANCE NOT
 ADDRESSED THAT A 4X FEE FOR PLAN REVIEW
 PORTION OF PERMIT FEE SHALL BE ACCESSED.
 THIS IS A REQUIRED FEE UNDER FS AND IS
 NOW ACCESSED. PLEASE SEE NUMEROUS
 COMMENTS FROM PREVIOUS TWO REVIEWS WERE
 NOT ADDRESSED.
 PLEASE SEE A FEE OF $6792.00 HAS NOW
 BEEN ATTACHED AND THIS FEE MUST BE PAID
 BEFORE RESUBMITTING PLANS. THIS IS
 REQUIRED UNDER FS 553.80(2)(B).
 PLEASE BE AWARE THE COPY OF ABOVE FS IS
 ATTACHEDONCE AGAIN.
  
 **PLEASE SEE ONE SET OF THE ELECTRICAL
 PLANS ARE BEING RETAINED FOR FILE.
 PLEASE SEE THESE MAY BE SENT TO THE
 BOARD OF ARCH'S FOR REVIEW.
  
 2)NOTE: PLEASE PROVIDE A COMPLETE
 CONTRACT SHOWING VALUATION FOR COMPLETE
 ELECTRICAL WORK AS SET FORTH ON PLANS.
 PLEASE SEE LOCAL ADMINISTRATIVE CODE/FBC
 104.6.5.
 PLEASE SEE FS 471.003, IF VALUE FOR
 ELECTRICAL SCOPE OF WORK IS $50K OR
 MORE, PLANS WILL BE REQUIRED TO BE DONE
 BY A PROFESSIONAL ENGINEER.
  
 3)NOTE: PLEASE SEE ONE SETOF PLANS
 HAVE MANY OF THE ABOVE REDLINED AT
 LOCATIONS OF COMMENTS ONCE AGAIN.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETSFOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  