Plan Review Notes
Plan Review Notes For Permit 04110624
Permit Number 04110624
Review Stop M
Sequence Number 2
Notes
Date Text
2005-02-03 00:00:00DENIED:
 PLEASE NOTE COMMENTS NOT ADDRESSED FROM
 PREVIOUS REVIEW DATED 12-4-04.PROVIDE
 A RESPONSE LETTER TO COMMENTS TO HELP
 EXPEDITE PLANS.
  
 2ND REQUEST:
 1.PROVIDE DETAIL FOR PENETRATIONS
 THROUGH RATED ASSEMBLIES.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS
 PER 2001 FBC(M) TABLE 403.3 OR 402.
 PROVIDE CALCULATIONS FOR ALL AREAS,
 COMMON AND RESIDENTIAL.
  
 4.PROVIDE OUTSIDE AIR INTAKE, DUCT
 LAYOUT, SIZE AND MATERIAL.
  
 5.RETURN AIR JUMPERS SHALL BE A
 MINIMUM OF 1 1/2 TIMES THE SQUARE
 INCHES OF THE SUPPLY AIR INTO THAT
 SPACE.ALL AIR INTO THE MASTER SUITE IS
 TO BE INCLUDED PER 2001 FBC(M)601.4
 EXCEPTION #1 & 3.
  
 6.INDICATE VENTILATION FOR THE
 STORAGE
 AREA ON THE SECOND FLOOR IN ACCORDANCE
 WITH 2001 FBC(M) TABLE 403.3.PLEASE
 INDICATE WHAT WILL BE STORED IN THE
 STORAGE AREA.
  
 7.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS REQUIRED.2001
 FBC(M)606.2.1 & 606.4.1 #2.
  
 8.PROVIDE SUBMITTAL FOR THE HOOD TO
 THE RANGE & HOOD INDICATED ON THE 1ST
 FLOOR KITCHEN.PLEASE NOTE, EXHAUST
 SHALL NOT TERMINATE ONTO THE WALKWAY.
  
 9.PROVIDE EQUIPMENT SCHEDULE FOR THE
 ALL OF THE EXHAUST FANS.
  
 10. IDENTIFY LOCATION OF THE AHU ON THE
 FIRST FLOOR.
  
 11. INDICATE LINE SIZE FOR THE LIQUID,
 SUCTION AND CONDENSATE LINES.
  
 12. CONDENSATE TO TERMINATE A MINIMUM
 OF
 12" AWAY FROM THE BUILDING STRUCTURE
 PER
 2001 FBC(M)1503.4.4.
  
 13. INDICATE TERMINATION OF ALL
 CONDENSATE LINES.CONDENSATE FROM THE
 7.5 TON SYSTEM ON THE 1ST FLOOR SHALL
 TERMINATE INTO THE STORM OR AN APPROVED
 DRYWELL PER CITY CODE SEC.90-125 (5).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.