| 2005-01-26 00:00:00 | *********** UNSAT 2ND REVIEW ********* |
| | |
| | PLEASE SEE MANY OF THE NOTES FROM |
| | PREVIOUS REVIEW STILL NEED TO BE |
| | ADDRESSED. |
| | |
| | 1)NOTE: NOTE #1 OK, ADDRESSED W/NOTE. |
| | |
| | 2)NOTE: NOTE #2 NO, SEE 424.3B |
| | |
| | 3)NOTE: NOTE #3 YES, HOWEVER LOAD CALCS |
| | FOR PANEL "D" ARE NOT PER 220 FOR |
| | COMMERICAL SPACE. PLEASE SEE NOTE# 4 |
| | FROM PREVIOUS REVIEW. |
| | ***NEW*** |
| | PLEASE SEE NOTE THAT LOAD CALCS HAVE |
| | BEEN SUBMITTED, PLEASE CORRELATE VOLTAGE |
| | AND LOAD CALCS FROM PANEL SCHEDULES TO |
| | LOADS ON RISER DIAGRM. |
| | |
| | 4)NOTE: NOTE #4 NO, PLEASE SEE PREVIOUS |
| | NOTE. |
| | |
| | 5)NOTE: NOTE #5, ? PANEL CH SEEMS TO NOW |
| | BE PANEL "D"> NO COMMENT. |
| | |
| | 6)NOTE: NOTE #6 NO, SEE PREVIOUS |
| | COMMENTS. #2 STILL SHOWN ON OCP TOO HIGH |
| | FOR RATING OF AWG ETC. |
| | |
| | 7)NOTE: NOTE #7 NO. SEE PREVIOUS NOTE. |
| | |
| | 8)NOTE: NOTE #8 NO. SEE PREVIOUS NOTE. |
| | |
| | 9)NOTE: NOTE #9 OK. |
| | |
| | 10)NOTE: NOTE #10 NO SEE PREVIOSU NOTE. |
| | |
| | 11)NOTE: NOTE #11 NO? SEE LOAD CALCS. |
| | SEE 240.4B |
| | |
| | 12)NOTE: NOTE #12 OK. |
| | |
| | 13)NOTE: NOTE #13 NO, SEE PREVIOUS NOTES |
| | ABOUT NOTE #21. |
| | |
| | 14)NOTE: NOTE #14 NO, SEE PREVIOUS. |
| | |
| | 15)NOTE: NOTE #15 OK. |
| | |
| | 16)NOTE: NOTE #16 OK. |
| | |
| | 17)NOTE: NOTE #17 ? ADDED AS NOTE, |
| | INSTEAD OF PANEL SCHEDULE AS PREVIOUS |
| | REQUEST. |
| | |
| | 18)NOTE: NOTE #18 OK |
| | |
| | 19)NOTE: NOTE #19 NO, SEE PREVIOUS |
| | NOTES. |
| | |
| | 20)NOTE: NOTE #20 OK. |
| | |
| | 21)NOTE: NOTE #21 NO, UNCLEAR, PLEASE |
| | ADD NOTE FOR CLEARENCE OF DISC'S PER |
| | 110.26. |
| | |
| | **** NEW NOTE**** |
| | |
| | 1)NOTE: PLEASE SEE ATTACHED COPY OF FS |
| | 553.80(2)(B). PLEASE SEE IF PLANS COME |
| | BACK WITH ANY OF THE SAME COMMENTS FROM |
| | TWO PREVIOUS REVIEWS NOT ADDRESSED, A 4X |
| | FEEFOR PLAN REVIEW PORTION OF PERMIT |
| | MUST BE ACCESSED PER FS. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWS WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF OLD PLANS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | |
| | |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |