Plan Review Notes
Plan Review Notes For Permit 04110624
Permit Number 04110624
Review Stop E
Sequence Number 2
Notes
Date Text
2005-01-26 00:00:00*********** UNSAT 2ND REVIEW *********
  
 PLEASE SEE MANY OF THE NOTES FROM
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
  
 1)NOTE: NOTE #1 OK, ADDRESSED W/NOTE.
  
 2)NOTE: NOTE #2 NO, SEE 424.3B
  
 3)NOTE: NOTE #3 YES, HOWEVER LOAD CALCS
 FOR PANEL "D" ARE NOT PER 220 FOR
 COMMERICAL SPACE. PLEASE SEE NOTE# 4
 FROM PREVIOUS REVIEW.
 ***NEW***
 PLEASE SEE NOTE THAT LOAD CALCS HAVE
 BEEN SUBMITTED, PLEASE CORRELATE VOLTAGE
 AND LOAD CALCS FROM PANEL SCHEDULES TO
 LOADS ON RISER DIAGRM.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE PREVIOUS
 NOTE.
  
 5)NOTE: NOTE #5, ? PANEL CH SEEMS TO NOW
 BE PANEL "D"> NO COMMENT.
  
 6)NOTE: NOTE #6 NO, SEE PREVIOUS
 COMMENTS. #2 STILL SHOWN ON OCP TOO HIGH
 FOR RATING OF AWG ETC.
  
 7)NOTE: NOTE #7 NO. SEE PREVIOUS NOTE.
  
 8)NOTE: NOTE #8 NO. SEE PREVIOUS NOTE.
  
 9)NOTE: NOTE #9 OK.
  
 10)NOTE: NOTE #10 NO SEE PREVIOSU NOTE.
  
 11)NOTE: NOTE #11 NO? SEE LOAD CALCS.
 SEE 240.4B
  
 12)NOTE: NOTE #12 OK.
  
 13)NOTE: NOTE #13 NO, SEE PREVIOUS NOTES
 ABOUT NOTE #21.
  
 14)NOTE: NOTE #14 NO, SEE PREVIOUS.
  
 15)NOTE: NOTE #15 OK.
  
 16)NOTE: NOTE #16 OK.
  
 17)NOTE: NOTE #17 ? ADDED AS NOTE,
 INSTEAD OF PANEL SCHEDULE AS PREVIOUS
 REQUEST.
  
 18)NOTE: NOTE #18 OK
  
 19)NOTE: NOTE #19 NO, SEE PREVIOUS
 NOTES.
  
 20)NOTE: NOTE #20 OK.
  
 21)NOTE: NOTE #21 NO, UNCLEAR, PLEASE
 ADD NOTE FOR CLEARENCE OF DISC'S PER
 110.26.
  
 **** NEW NOTE****
  
 1)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B). PLEASE SEE IF PLANS COME
 BACK WITH ANY OF THE SAME COMMENTS FROM
 TWO PREVIOUS REVIEWS NOT ADDRESSED, A 4X
 FEEFOR PLAN REVIEW PORTION OF PERMIT
 MUST BE ACCESSED PER FS. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD PLANS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]