Plan Review Notes
Plan Review Notes For Permit 04110624
Permit Number 04110624
Review Stop B
Sequence Number 2
Notes
Date Text
2005-01-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110624
 ADD: 1318 HENRIETTA AVE
 CONT: RANDOLPH & DEWDNEY
 TEL: (561)441-1186
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT # 1 FROM THE PREVIOUS
 REVIEW,
 SHEET A-2 CORRECT EGRESS WINDOW
 STATEMENT ON THE GROUND FLOOR THE
 MINIMUM CLEAR OPENING SIZE IS 5'-0"
 NOT "THE NET CLEAR OPENING IN NO CASE
 BE
 LESS THAN 4'-0" SQ FT".
 2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL
 HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR.
 3) COMMENT# 2 FROM THE PREVIOUS REVIEW,
 DEALS WITH THE HANDICAPPED BATHROOM
 REQUIREMENTS MISSING A COMMENT OR
 DETAIL
 INCLUDING THE REAR GRAB BAR AT THE
 WATER
  
 CLOSET.
 3) COMMENT# 3 FROM THE PREVIOUS REVIEW
 PLANS ARE NOT CLEAR ON THE FRONT ENTRY,
 ELEVATION INDICATE A STOOP OR LANDING
 THEN A STEP INTO THE LOBBY,
 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY. EXPLAINRATIONAL OR INDICATE
 A COMPLIANT RAMP.
  
 4) COMMENT# 4 FROM THE PREVIOUS REVIEW,
 FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A-2 PROVIDE THE MEAN ROOF HEIGHT.
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, SHEET
 A-8DETAIL# 3 INDICATES AN EXTERIOR
 BLOCK
 WALL 4 BAR BEAM AND LEDGERS BUCKET AND
 FLOOR TRUSSES, PLANS LACK THE ATTCHMENT
 OF DOUBLE LEDGER TO BEAM AND TYPE OF
 BUCKET FOR FLOOR TRUSSES. SAME DETAIL
 MISSING APPROVED HANGERS FROM THE 3
 MEMBER GIRDER?
  
 6) COMMENT # 6 FROM THE PREVIOUS
 REVIEW,
 A-2 THE DESIGN OF THE EXTERIOR STAIR
 DOESN'T MET THE REQUIREMENT FOR A
 SINGLE
  
 STAIRWAY IN 1026.1 BECAUSE OF THE 1ST
 REQUIREMENT BEING THE MAXIMUM LENGTH OF
 TRAVEL TO REACH THE EXIT FROM THE
 ENTRANCE DOOR TO ANY UNIT SHALL NOT
 EXCEED 30 FT. SO (2) STAIRWAYS ARE
 REQUIRED.
 THE PROBLEM WITH THE STAIR DESIGN
 IS
 1006.2.2 REQUIRES THE STAIRS SHALL BE
 LOCATED THAT THE ENTRANCES AND ALL
 PORTIONS OF THE STAIRWAYS ON EACH LEVEL
 ARE A DISTANCE APART EQUAL TO NOT LESS
 THAN 1/2 OF THE LENGHT OF THE MAXIMUM
 OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA SERVED.
 SO INFACT THE PLAN MAY INDICATE (2)
 STAIRWAYS IN ELEVATION,BY DEFINITION
 THERE IS ONLY ONE.
  
 7) COMMENT# 7 FROM THE PREVIOUS REVIEW,
 A-2 MULTI PURPOSE ROOM# 2 ENTRY DOOR,
 SEE11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING
 CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 8)SHEET A-3 & A-4 GUARD RAIL
 EXTENTIONS:
 1007.5.5. HANDRAILS SHALL EXTEND AT
 LEAST 12 INCHES HORIZONTALLY BEYOND THE
 TOP RISER OF A FLIGHT. .AT THE BOTTOM,
 THE HANDRAIL SHALL CONTINUE TO SLOPE
 FOR
 A DISTANCE OF THE DEPTH OF ONE TREAD
 FROM THE BOTTOM RISER.
  
 9) COMMENT# 15 FROM THE PREVIOUS
 REVIEW:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B1) ROOFING ASSEMBLIES- A-8 INDICATES
 THE USE OF MONIER VILLA ROLL"S" VS THE
 PRODUCT APPROVAL SUBMITTEDFOR A
 ENTEGRA ESTATE "S" TILE
 B2) A-8 ARCHETECT ALSO PROVIDE A
 OPTION OF TIMBERLINE ASPHALT TILE, THE
 LOADING FOR TILE VS SHINGLES ARE NOT THE
 SAME.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026