2004-12-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-2 KITCHEN SINK SHALL COMPLY
 WITH SECTION 4.24 AND ALL SUBSECTIONS.
 PLEASE SUBMIT A DETAIL.
 2) SHT A-2 DRINKING FOUNTAIN SHALL
 COMPLY WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS. SUBMIT A DETAIL. ALSO SHOW
 COMPLIANCE WITH SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
 3) TABLE 403.1 AUTOMATIC CLOTHS WASHER
 CONNECTIONS ARE REQUIRED. SHOW ON THE
 FLOOR PLAN, SANT. RISER DIAGRAM AND THE
 WATER RISER DIAGRAM.
 4) SUBMIT A WATER RISER DIAGRAM REQUIRED
 BY SECTION 104.3.1.1. SHOW ALL PIPE
 SIZES, VALVES AND WATER HAMMER ARRESTORS
 PER SECTION 606 & 604.9.
 5) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2.
 6) THERMAL EXPANSION CONTROL IS REQUIRED
 AT ALL WATER HEATERS PER SECTION
 607.3.2
 7) SECTION 909.1 THE KITCHEN SINK SHALL
 NOT DRAIN THROUGH THE WET-VENTED
 HORIZONTAL DRAIN OF THE BATHROOM
 FIXTURES. THE KITCHEN SINKS SHALL
 DISCHARGE DOWNSTREAM OF THE BATHROOM
 FIXTURES.
 8) PLEASE NOTE THAT MOST OF THESE
 COMMENTS WERE STATED IN THE REVIEW OF
 PERMIT NUMBER 03011199.
  
  
  
  