| 2004-12-11 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A-2 KITCHEN SINK SHALL COMPLY |
| | WITH SECTION 4.24 AND ALL SUBSECTIONS. |
| | PLEASE SUBMIT A DETAIL. |
| | 2) SHT A-2 DRINKING FOUNTAIN SHALL |
| | COMPLY WITH SECTION 11-4.15 AND ALL |
| | SUBSECTIONS. SUBMIT A DETAIL. ALSO SHOW |
| | COMPLIANCE WITH SECTION 11-4.1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY |
| | BENDING OR STOOPING. |
| | 3) TABLE 403.1 AUTOMATIC CLOTHS WASHER |
| | CONNECTIONS ARE REQUIRED. SHOW ON THE |
| | FLOOR PLAN, SANT. RISER DIAGRAM AND THE |
| | WATER RISER DIAGRAM. |
| | 4) SUBMIT A WATER RISER DIAGRAM REQUIRED |
| | BY SECTION 104.3.1.1. SHOW ALL PIPE |
| | SIZES, VALVES AND WATER HAMMER ARRESTORS |
| | PER SECTION 606 & 604.9. |
| | 5) AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE. SECTION 608.13.2. |
| | 6) THERMAL EXPANSION CONTROL IS REQUIRED |
| | AT ALL WATER HEATERS PER SECTION |
| | 607.3.2 |
| | 7) SECTION 909.1 THE KITCHEN SINK SHALL |
| | NOT DRAIN THROUGH THE WET-VENTED |
| | HORIZONTAL DRAIN OF THE BATHROOM |
| | FIXTURES. THE KITCHEN SINKS SHALL |
| | DISCHARGE DOWNSTREAM OF THE BATHROOM |
| | FIXTURES. |
| | 8) PLEASE NOTE THAT MOST OF THESE |
| | COMMENTS WERE STATED IN THE REVIEW OF |
| | PERMIT NUMBER 03011199. |
| | |
| | |
| | |
| | |