2004-12-04 00:00:00DENIED:
 1.PROVIDE DETAIL FOR PENETRATIONS
 THROUGH RATED ASSEMBLIES, I.E.
 CEILING/FLOOR & WALL.
  
 2.PLAN DOES NOT INDICATE LOCATION
 AND
 DETAIL OF FIRE DAMPERS AS REQUIRED PER
 2001 FBC(M)607.6.
  
 3.PROVIDE OUTSIDE AIR CALCULATIONS
 PER
 2001 FBC(M) 403.3.PROVIDE CALCS FOR
 RESIDENTIAL AND COMMERCIAL AREA.
  
 4.INDICATE OUTSIDE AIR INTAKE, DUCT
 LAYOUT, SIZE AND MATERIAL.
  
 5.RETURN AIR JUMPERS SHALL BE A
 MINIUM
 OF 1 1/2 TIMES THE SQUARE INCHES OF THE
 SUPPLY AIR INTO THAT SPACE.
  
 6.INDICATE MINIMUM VENTILATION FOR
 THE
 STORAGE AREA INDICATED ON THE 2ND
 FLOOR.
  
 7.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR THE 1ST FLOOR 7.5 TON
 UNIT.
 INDICATE LOCATION OF DUCT SMOKE
 DETECTOR.
  
 8.NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS REQUIRED FOR
 DUCT SMOKE DETECTORS PER NFPA 90A.
  
 9.PROVIDE SUBMITTAL FOR THE
 RANGE/HOOD
 INDICATED ON THE 1ST FLOOR COMMON AREA
 KITCHEN.
  
 10. PLANS ARE TO BE SIGNED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN PER CITY
 AMENDMENTS TO THE 2001 FBC 104.2.1.
  