| 2004-12-04 00:00:00 | DENIED: |
| | 1.PROVIDE DETAIL FOR PENETRATIONS |
| | THROUGH RATED ASSEMBLIES, I.E. |
| | CEILING/FLOOR & WALL. |
| | |
| | 2.PLAN DOES NOT INDICATE LOCATION |
| | AND |
| | DETAIL OF FIRE DAMPERS AS REQUIRED PER |
| | 2001 FBC(M)607.6. |
| | |
| | 3.PROVIDE OUTSIDE AIR CALCULATIONS |
| | PER |
| | 2001 FBC(M) 403.3.PROVIDE CALCS FOR |
| | RESIDENTIAL AND COMMERCIAL AREA. |
| | |
| | 4.INDICATE OUTSIDE AIR INTAKE, DUCT |
| | LAYOUT, SIZE AND MATERIAL. |
| | |
| | 5.RETURN AIR JUMPERS SHALL BE A |
| | MINIUM |
| | OF 1 1/2 TIMES THE SQUARE INCHES OF THE |
| | SUPPLY AIR INTO THAT SPACE. |
| | |
| | 6.INDICATE MINIMUM VENTILATION FOR |
| | THE |
| | STORAGE AREA INDICATED ON THE 2ND |
| | FLOOR. |
| | |
| | 7.FAN SHUTDOWN BY DUCT SMOKE DETECTOR |
| | REQUIRED FOR THE 1ST FLOOR 7.5 TON |
| | UNIT. |
| | INDICATE LOCATION OF DUCT SMOKE |
| | DETECTOR. |
| | |
| | 8.NOTIFICATION TO ALARM/STROBE IN |
| | NORMALLY OCCUPIED AREAS REQUIRED FOR |
| | DUCT SMOKE DETECTORS PER NFPA 90A. |
| | |
| | 9.PROVIDE SUBMITTAL FOR THE |
| | RANGE/HOOD |
| | INDICATED ON THE 1ST FLOOR COMMON AREA |
| | KITCHEN. |
| | |
| | 10. PLANS ARE TO BE SIGNED BY THE PERSON |
| | RESPONSIBLE FOR THE DESIGN PER CITY |
| | AMENDMENTS TO THE 2001 FBC 104.2.1. |
| | |