| Plan Review Notes For Permit 04110624 |
| Permit Number |
04110624 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-16 00:00:00 | FIRE REVIEW PLEASE REF NFPA 101 LIFE | | | SAFETY CODE 2000 EDITION | | | | | | 1) DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2) DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. | | | | | | 3) BUILDING ADDRESSES ARE REQUIRED. | | | COULD NOT LOCATE THEM ON ELEVATION | | | DRAWINGS. | | | | | | 4) PLEASE INDICATE THE INTERIOR WALL AND | | | CEILING FINISH CLASS "A", CLASS "B", OR | | | CLASS "C". | | | | | | 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS FOR BALCONY RAILINGS. | | | | | | 6) STAIRS SHALL HAVE HANDRAILS ON EACH | | | SIDE. | | | | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|