| 2004-11-19 00:00:00 | *********** UNSAT ************ |
| | |
| | PLEASE SEE SOME OF THE NOTES FROM |
| | REVIEW |
| | UNDER PERMIT #03011199 ARE THE SAME. |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO |
| | BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2)NOTE: PLEASE SEE OCP FOR AHU'S PER |
| | 424.3B, CLUBHOUSE UNIT. PLEASE ALSO SEE |
| | 50A OCP FOR UNIT #3 FOR A 5KW UNIT.? |
| | PLEASE CORRELATE SIZES OF ALL A/C UNITS |
| | WITH MECHANICAL PLANS. |
| | |
| | 3)NOTE: PLEASE SEE ALL PANEL SCHEDULES |
| | DO NOT INCLUDE LOAD INFORMATION AT THE |
| | BOTTOM.? |
| | 215.5 |
| | |
| | |
| | 4 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | PLEASE INDICATE WITH THE MIXED USE. |
| | NO LOAD CALCS SHOWN FOR CLUBHOUSE |
| | PANEL? |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE IDENTIFY CH PANEL. |
| | |
| | 6)NOTE: PLEASE CORRELATE OCP ON METER |
| | CENTER AND ALL PANELS. SOME SHOW 150A, |
| | 100A PANELS ALL WITH 200A BREAKERS |
| | FEEDING THEM?? |
| | 310.16,240.4B |
| | PLEASE ALSO SEE #2 AWG ON 200A BRKR. #2 |
| | PER 310.16 IS RATED AT 115A'S?? |
| | |
| | 7)NOTE: PLEASE SEE THERE IS ONLY ONE |
| | SMALL APPLIANCE LOAD ON PANEL SCHEDULE? |
| | PLEASE SEE TWO MIN AS INDICATE IN LOAD |
| | CALCS FOR UNITS. 220.16,210.11C1, |
| | 210.52B1 |
| | |
| | 8)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL |
| | SCHEDULES. |
| | PLEASE SEE SD'S ETC.OUTSIDE LTS? |
| | PLEASE SEE CIRCUITING FOR CU FOR |
| | CLUBHOUSE, DOES NOT CORRELATE W/ PANEL |
| | SCHEDULE. SHOWN ON TWO DIFFERENT SIDES |
| | OF THE PANEL. |
| | |
| | 9)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPT ON 2' OF WALL, UNIT #1 |
| | |
| | 10)NOTE: PLEASE SEE CIRCUITING FOR |
| | DINING RM RECEPTS.210.52B1, 220.16 |
| | |
| | 11)NOTE: PLEASE SEE SEC'S TO BE SIZED |
| | PER 310.16, 240.4B |
| | |
| | 12)NOTE: PLEASE SEE 250.50, THIS ALSO |
| | REQUIRES FOOTER STEEL. RISER INDICATES |
| | BLDG STEEL? |
| | |
| | |
| | 13)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 2002 NEC 210.12 |
| | PLEASE SEE NOTE#21 ON PLANS. PLEASE |
| | ADJUST. |
| | |
| | 14)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF EM/EXT LTS.PLEASE ALSO |
| | ADJUST PANEL SCHEDULE. |
| | |
| | 15)NOTE: PLEASE INCLUDE ALL INFORMATION |
| | ON TITLE BLOCK AS REQUIRED UNDER FAC |
| | 61G1-16.004. |
| | PLEASE SEE THAT THIS IS REQUIRED ON ALL |
| | SHEETS WHEATHER OR NOT COMMENT IS MADE |
| | BY OTHER REVIEWER(S). |
| | PLEASE SEE FBC 104.2.1 FOR ALL PLANS, |
| | INCLUDING MECHANICAL. |
| | |
| | 16)NOTE: PLEASE SEE SOME PANEL |
| | SCHEDULES INDICATE PANEL LOCATIONS AS |
| | BEING A"GARAGE"? HOWEVER , COULD NOT |
| | LOCATE ANY GARAGES ON PLANS? MISPRINT?? |
| | |
| | |
| | 17)NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE(S). PER 210.52D, 210.11C3 |
| | MUST BE 20A #12 |
| | |
| | 18)NOTE: PLEASE SHOW LOCATION OF CH |
| | PANEL ON PLANS. THIS COULD NOT BE |
| | LOCATED. |
| | |
| | 19)NOTE: PLEASE SEE SOME LTS ARE SHOWN |
| | ON PLANS ON THE SAME SWITCH LEG,HOWEVER |
| | THEY ARE ON TWO SEPARATE CIRCUITS?? |
| | THIS WILL NOT WORK, THESE MUST BE ONTHE |
| | SAME CIRCUIT OR SEPARATE SWITCHES. |
| | |
| | 20)NOTE: PLEASE SEE WF/WATER COOLER IS |
| | SHOWN ON GEN LT CIRCUIT. PLEASE VERIFY |
| | THISAS IT MAY BE REQUIRED TO BE ON A |
| | SEPARATE CIRCUIT. |
| | |
| | 21)NOTE: PLEASE SHOW CLEARENCE FOR A/C |
| | DISCONNECTS PER 110.26 |
| | |
| | 22)NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE SUBMIT ONE COPY OF OLD SHEETS |
| | FOR REFERENCE ONLY. |
| | |
| | 23)NOTE: PLEASE SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER REVIEWERS WHICH MAY |
| | HAVE AN AFFECT ON ELECTRICAL PLANS. |
| | PLEASE SEE ANY FIRE REVIEW COMMENTS. |
| | |
| | PLEASE SEE ONE SET HAS MOST OF THE |
| | ABOVE COMMENTS REDLINED IN THE AREAS AS |
| | NOTED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | ME. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |