| Date |
Text |
| 2004-12-13 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04110624 |
| | ADD: 1318 HENRIETTA AV |
| | CONT: RANDOLPH & DEWDNEYCONST |
| | TEL: (561)441-1182 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-2 CORRECT EGRESS WINDOWS |
| | STATMENT FOR 2ND FLOOR WINDOWS, |
| | 2001 FL BLD CODE, 1005.4: |
| | PROVIDE EMERGENCY EGRESS WINDOWS IN |
| | SLEEPING ROOMS WITH A MINIMUM NET CLEAR |
| | OPENING HEIGTH OF 24" AND NET CLEAR |
| | OPENING WIDTH OF 20" AND A NET CLEAR |
| | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR |
| | OPENINGS ARE PERMITTED TO HAVE A NET |
| | CLEAR OPENING OF 5.0 SQ. FT. SILL |
| | HEIGTH |
| | SHALL NOT BE MORE THAN 44 " ABOVE THE |
| | FINISH FLOOR. |
| | |
| | 2) HANDICAPPED RESTROOMS- SEE CHAPTER |
| | 11 |
| | FIGURE 30E FOR LENGTH OF REQUIRED GRAB |
| | BARS FOR SIDE AND REAR LOCATIONS. |
| | |
| | 3) PLANS ARE NOT CLEAR AS TO LANDING |
| | LEVELS FOR FRONT AND SIDE ENTRY 1ST FL. |
| | 11-4.1.3(1) AT LEAST ONE ACCESSIBLE |
| | ROUTE COMPLYING WITH 11-4.3 SHALL |
| | CONNECT ACCESSIBLE BUILDING OR FACILITY |
| | ENETRANCES WITH ALL ACCESSIBLE SPACES |
| | AND ELEMENTS WITHIN THE BUILDING OR |
| | FACILITY. SEE A-2. |
| | |
| | 4) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, SHEET |
| | A-2 PROVIDE THE MEAN ROOF HEIGHT. |
| | |
| | 5) SHEET A-2 COMMENT "STAIRWAYS COMPLY |
| | WITH THE REQUIREMENTS OF 1026.1" |
| | 104.2.1 W.P.B. ADMINISTRATIVE CODE |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR |
| | OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL |
| | TO |
| | CONFORMITY WITH THE TECHNICAL CODES. |
| | SUCH INFORMATION SHALL BE |
| | SPECIFIC |
| | AND THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE |
| | TERM "LEGAL" OR ITS RQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". |
| | |
| | 6) SHEET A-2 THE DESIGN OF THE EXTERIOR |
| | STAIR, DOESN'T MEET THE DEFINITION OF A |
| | SINGLE STAIRWAY IN 1026.1 BECAUSE OF |
| | THE |
| | 1 ST REQUIREMENT BEING THE MAXIMUM OF |
| | TRAVEL TO REACH THE EXIT FROM THE |
| | ENTRANCE DOOR TO ANY UNIT SHALL NOT |
| | EXCEED 30 FEET. |
| | THE PROBLEM WITH THE DESIGN OF THIS |
| | STAIRWAY FOR (2) EXIT STAIRS, 1006.2.2, |
| | REQUIRES, THE STAIRWAYS SHALL BE |
| | LOCATED |
| | THAT THE ENTRANCES AND ALL PORTIONS OF |
| | THE STAIRWAYS ON EACH LEVEL ARE A |
| | DISTANCE APART EQUAL TO NOT LESS THAN |
| | 1/2 OF THE LENGHT OF THE MAXIMUM |
| | OVERALL DIAGONAL DIMENSION OF THE |
| | BUILDING OR AREA SERVED. |
| | |
| | 7) SHEET A-2 MULTI PURPOSE ROOM# 2, SEE |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL.REQUIRES 18" ON THE SWING |
| | SIDE OF LATCH. |
| | |
| | 8) SHEET A-3 GUARD RAIL EXTENSIONS: |
| | 1007.5.5. HANDRAILS SHALL EXTEND AT |
| | LEAST 12 INCHES HORIZONTALLY BEYOND THE |
| | TOP RISER OF A FLIGHT. .AT THE BOTTOM, |
| | THE HANDRAIL SHALL CONTINUE TO SLOPE FOR |
| | A DISTANCE OF THE DEPTH OF ONE TREAD |
| | FROM THE BOTTOM RISER. |
| | |
| | 9) 1007.5.2 STAIRWAYS SHALL HAVE HAND- |
| | RAILS ON EACH SIDE. |
| | |
| | 10) 1608.2.3 THE GUARDRAIL SYSTEM SHALL |
| | BE DESIGNED AND CONSTRUCTED TO RESIST A |
| | 200 LB CONCENTRATED HORIZONTAL LOAD |
| | APPLIED ON A 1 SQ FT AREA AT ANY POINT |
| | IN THE SYSTEM INCLUDING INTERMEDIATE |
| | RAILS OR OTHER ELEMENTS SERVING THIS |
| | PURPOSE. SEE A-8. |
| | |
| | 11)A-4STAIR NOTE " STAIR RAILING |
| | |
| | AND STAIRS TO CODE", 104.2.1 |
| | W.P.B. ADMINISTRATIVE CODE DRAWINGS & |
| | SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR |
| | OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. |
| | SUCH INFORMATION SHALL BE SPECIFIC AND |
| | THE TECHNICAL CODES "SHALL NOT BE CITED |
| | AS A WHOLE OR IN PART, NOR THE TERM |
| | "LEGAL" OR ITS RQUIVALENT BE USED AS A |
| | SUBSTITUTE FOR SPECIFIC INFORMATION". |
| | |
| | 12) WALL TO CBS CONNECTION, INDICATES |
| | THE USE OF HUGHES CONNECTIONS, PLEASE |
| | CORRECT HUGHES HAS BEEN OUT OF BUSINESS |
| | |
| | SINCE 1999. |
| | |
| | 13) A-8 DROPPED CEILING DETAIL CORRECT, |
| | BRACING AS REQUIRED AND PROVIDE THE |
| | INFORMATIONREQUIRED FOR A DROP CEILING, |
| | ALLOWABLE CEILING SPANS, DEFLECTION |
| | LIMIT L/240, CEILINGPSF, WILL MIDSPAN |
| | SUPPORTS BE USED. SIZE & THICKNESS OF |
| | MATERIAL USED.2504.5.1/ ASTM C 754. |
| | |
| | 14)1503.4.4 PROTECTION AGAINST DECAY & |
| | TERMITES. CONDENSATE LINES & ROOF DOWN |
| | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| | AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| | TENSIONS, OR SPLASH BLOCKS. |
| | |
| | 15) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 16) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A)TRUSS ANCHOR SCHEDULE |
| | B) ROOFING ASSEMBLIES- THE REFRENCED |
| | ROOF TILE BY ARCHITECT DOES NOT |
| | MATCH SUBMITTAL |
| | |
| | 17) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |