| Plan Review Notes For Permit 04110604 |
| Permit Number |
04110604 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-12-16 00:00:00 | *********** PROVISO/REVISION ********** | | | | | | 1)NOTE: PLEASE REVISE RISER TO INCLUDE | | | NEW PANEL AT MAIN HOUSE. | | | PLEASE SEE 225.31 FOR MCB REQUIRED AT | | | DETACHED BLDG. | | | PLEASE SEE 250.32 FOR GROUNDING AT | | | DETACHED BLDG. | | | | | | 2)NOTE: PLEASE SEE SEC'S TO BE INCREASED | | | TO 250 MCM PER 310.15B6, 240.4B | | | | | | 3)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | | CONDUCTOR PER 250.66 (#2). | | | | | | PLEASE REVISE PLANS ALONG WITH ANY OTHER | | | REVISIONS BEFORE ROUGH. | | | IF THERE ARE ANY QUESTIONS, PLEASE | | | CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|