| 2004-11-22 00:00:00 | ************ UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SHOW LOCATION OF |
| | SERVICE. |
| | PLEASE SEE PLANS DO NOT INDICATE IF |
| | THESE BLDGS ARE ATTACHED OR DEATCHED? |
| | IF DETACHED PLEASE INCLUDE COMPLETED |
| | RISER DIAGRAM SHOWING ALL SERVICE |
| | EQUIPMENT. PLEASE SEE 225.31,250.32 ETC |
| | FOR DEATCHED BLDGS. |
| | |
| | |
| | 2)NOTE: PLEASE SHOW ALL RECEPTS |
| | SERVING KITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECT- -ED PER 210.8A-6 |
| | |
| | |
| | 3)NOTE: PLEASE SEE RECEPTS SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5 |
| | |
| | 4)NOTE: PLEASE INCLUDE ALL A/C EQUIPMENT |
| | ON PLANS. PLEASE INCLUDE ALL DISC'S |
| | 440.11 AND GFI RECEPT(S) PER 210.63. |
| | |
| | 5)NOTE: PLEASE SEE MISSING FRONT AND |
| | REAR RECEPTS. 210.52E |
| | |
| | 6)NOTE: PLEASE SIZE SEC'S PER 310.15B6, |
| | 250 MCM MIN FOR 275A SERVICE. PLEASE |
| | ALSO SEE 240.4 |
| | |
| | 7)NOTE: PELASE ADJUST GEC PER 250.66. |
| | #2 |
| | |
| | 8)NOTE: PLEASE SEE 422.17 FOR WATER |
| | HEATERIN CLOSET. MUST HAVE SEPARATION |
| | FROM COMBUSTIBLES. |
| | |
| | 9)NOTE:PLEASE SEE ALL PLANS/DRAWINGS, |
| | SHEETS MUST CONTAIN THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSONRESPONSIBLE FOR |
| | PLANS. |
| | FBC 104.2.1 |
| | |
| | 10)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | ATTACHMENTS, GRND RODS, COLD WATER? |
| | 250.50 |
| | |
| | 11)NOTE: PLEASE SEE UPPER BATH RECEPT TO |
| | ALSO BE GFI PROTECTED.210.8 |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |