| Date |
Text |
| 2004-11-27 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | |
| | 1) MORE INFORMATION IS REQUIRED. PERMIT |
| | APPLICATION STATES "INSTALL WATER HEATER |
| | ELECTRIC OUTLETS", BUT IT SEEMS THAT |
| | MORE WORK IS SHOWN ON THE PLANS. WITH |
| | THE ADDITION OF A SANITARY RISER DIAGRAM |
| | IT SEEMS THAT A BATHROOM IS BEING |
| | ADDED. |
| | ALSO IT SEEMS THAT A WASH MACHINE IS |
| | BEING ADDED TO THE HOUSE. WILL THE |
| | BATHROOM BE FRAMED IN OR IS IT |
| | EXISTING? |
| | 2) SHT PL:1 SANITARY RISER DIAGRAM DOES |
| | NOT MEET CODE REQUIREMENTS. |
| | A) PLEASE SHOW ALL PIPE SIZES AND |
| | IDENTIFY ALL FIXTURES. SECTION 104.2.1 |
| | B) TRAPS ARE REQUIRED AT THE SHOWER, |
| | THE LAV., AND THE WASH MACHINE. SECTION |
| | 1002.1 |
| | C) THE WASH MACHINE REQUIRES A |
| | STANDPIPE AND SHALL HAVE A CLEANOUT |
| | INSTALLED 4 FEET ABOVE THE FLOOR FOR |
| | ACCESS. SECTIONS 1002.1 & 708.10 |
| | D) THE TWO 2" DRAINS ARE NOT VENTED, |
| | AND PIPED AS SUCH WILL BE AN "S" TRAP. |
| | SECTIONS 902.1 & 1002.3(5) |
| | E) ONLY THE FIXTURES WITHIN THE |
| | BATHROOM GROUPS SHALL CONNECT TO THE |
| | WET-VENTED HORIZONTAL BRANCH DRAIN. ANY |
| | ADDITIONAL FIXTURES SHALL DISCHARGE |
| | DOWNSTREAM OF THE WET VENT. SECTION |
| | 909.1 (THE WASH MACHINE SHALL CONNECT |
| | DOWNSTREAM OF THE BATHROOM FIXTURES). |
| | 3) ALL DRAWINGS SHALL BEAR THE NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | THE DESIGN. SECTION 104.2.1 |
| | |
| | |