| 2004-12-16 00:00:00 | FIRE REVIEW PLEASE REF NFPA 101 LIFE | | | SAFETY CODE 2000 EDITION | | | | | | 1) EXIT DOORS ARE REQUIRED TO SWING IN | | | DIRECTION OF EGRESS TRAVEL WHERE | | | SERVING | | | A ROOM OR AREA WITH AN OCCUPANT LOAD OF | | | 50 OR MORE. | | | | | | 2) A DOOR SHALL SWING IN THE DIRECTION | | | OF TRAVEL WHERE USED IN AN EXIT | | | ENCLOSURE. AND DURING ITS SWING, ANY | | | DOOR IN A MEANS OF EGRESS SHALL LEAVE | | | NOT LESS THAN ONE-HALF OF THE REQUIRED | | | WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, | | | OR LANDING, WHEN FULLY OPEN. | | | | | | 3) INTERIOR WALL AND CEILING FINISH | | | COMPLYING WITH 10.2.3 SHALL BE CLASS | | | "A" | | | OR CLASS "B" IN EXITS AND ENCLOSED | | | CORRIDORS FURNISHING ACCESS TO EXITS; | | | AND CLASS "A", CLASS "B", OR CLASS "C" | | | IN OFFICE AREAS. | | | | | | 4) SEPARATE PLANS AND PERMIT | | | APPLICATIONS ARE REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM SYSTEMS | | | REMODEL. | | | | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|