2004-12-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHTS A1.1 & A4.1 DETAIL K8 SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH THE
 FOLLOWING REQUIREMENTS FOR THE BREAK
 ROOM SINK PER SECTION 11-4.24 AND ALL
 SUBSECTIONS.
 11-4.24.3 KNEE CLEARANCE.
 11-4.24.4 SINK DEPTH.
 11-4.24.5 CLEAR FLOOR SPACE. - FORWARD
 APPROACH REQUIRED.
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 2) ALL SHEETS - THE BUSINESS LICENSE IS
 REQUIRED ON THE TITLE BLOCK. FAC
 61G1-16.004(2) & FS 481.219
 3) SHT P-2 WATER DIST. RISER. AIR
 CHAMBERS ARE NOT APPROVED. SECTION 604.9
 SEE PLUMBING SPECIFICATIONS NOTES 7 AND
 8. REMOVE ALL REFERENCE TO AIR
 CHAMBERS.
 SECTION 104.2.1.
  
  
  