| Plan Review Notes For Permit 04110542 |
| Permit Number |
04110542 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-10 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHTS A1.1 & A4.1 DETAIL K8 SUBMIT A | | | DETAIL SHOWING COMPLIANCE WITH THE | | | FOLLOWING REQUIREMENTS FOR THE BREAK | | | ROOM SINK PER SECTION 11-4.24 AND ALL | | | SUBSECTIONS. | | | 11-4.24.3 KNEE CLEARANCE. | | | 11-4.24.4 SINK DEPTH. | | | 11-4.24.5 CLEAR FLOOR SPACE. - FORWARD | | | APPROACH REQUIRED. | | | 11-4.24.6 EXPOSED PIPES AND SURFACES. | | | 2) ALL SHEETS - THE BUSINESS LICENSE IS | | | REQUIRED ON THE TITLE BLOCK. FAC | | | 61G1-16.004(2) & FS 481.219 | | | 3) SHT P-2 WATER DIST. RISER. AIR | | | CHAMBERS ARE NOT APPROVED. SECTION 604.9 | | | SEE PLUMBING SPECIFICATIONS NOTES 7 AND | | | 8. REMOVE ALL REFERENCE TO AIR | | | CHAMBERS. | | | SECTION 104.2.1. | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|