2004-12-09 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) 713.13 F.S.A NOTICE OF
 COMMENCEMENT SHALL BE RECORDED AT PALM
 BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT
 CAN BE ISSUED. BLANK FORMS ARE AVAILABLE
 FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST
 BE RE-RECORDED IF THE DESCRIBED
 IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2) 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3) FBC 1004ARRANGEMENT AND NUMBER OF
 EXITS, SHEET A1.1.THE KEY NOTES STATE
 THAT THE DOOR FROM THE WAITING ROOM IS
 TO BE "..LOCKED/SECURED".ANNOTATE THE
 PLAN OR SUBMIT A SEPARATE LIFE SAFETY
 PLAN TO CLARIFY THE EXITING.IS
 BREAKROOM DOOR "EX2" A FIRE EXIT
 LEADING
 TO THE 'STREET'?PLEASE CLARIFY.
  
 4) FBC 11-4.24.3BREAKROOM SINK.
 AMEND
 DETAIL J6 (SHEET A3.1) AND/OR THE FLOOR
 PLAN (SHEET A1.1) TO SHOW MIN. 30" WIDE
 X 19" DEEP KNEE CLEARANCE UNDER THE
 SINK.IT IS NOTED THAT THE REQUIRED
 MIN. 27" HEIGHT HAS ALREADY BEEN SHOWN
 ON SHEET A3.1 BUT DETAIL A11 (SHEET
 A4.1) DOES NOT CONCUR AND SHOULD BE
 STRUCK OUT IF NOT APPLICABLE.PLEASE
 CLARIFY.ALSO, ANNOTATE THE PLANS TO
 SHOW A MAX. SINK BOWL DEPTH OF 6.5" AND
 ANNOTATE THE PLANS TO STATE THAT THE
 SINK IS "ACCESSIBLE".
  
 5) FBC 2405.2SHEET A3.1, DOOR
 SCHEDULE
 DOORS 3 AND 4 TYPE C AND D RESPECTIVELY
 (BOTH GLAZED DOORS) BUT THE SCHEDULE
 CALLS UP 'MATERIAL' AND 'FINISH' NOTE
 #1.SHOULD THIS NOT BE NOTE #3 WHICH
 CALLS FOR TEMPERED GLASS AND STATES THE
 REQUIRED 3/4-HOUR FIRE-RATING REQUIRED
 FOR DOOR 4?NOTE DOOR 3 DOES NOT
 REQUIRE FIRE-RATING.AMEND THE
 SCHEDULE
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL
 INFO
 TELEPHONE: (561) 805 6716ROBERT
 BROWN
 E-MAIL: [email protected]