Text |
| 2004-12-07 00:00:00 | DENIED |
| | |
| | 1) THE ENERGY CALC. FORMS LIST R19 |
| | INSULATION AND THE PLANS SPECIFY R30. |
| | PLEASE CORRECT. |
| | |
| | 2) THE ENERGY CALCS DO NOT LIST THE 2X6 |
| | EXTERIOR WALLS WITH THE RI9 INSULATION. |
| | |
| | 3) THE BOTTOM OF FOOTING IS REQUIRED TO |
| | BE A MINIMUM OF 12" BELOW FINISH GRADE |
| | PER FBC 1804.1.3. REVISE WALL SECTIONS |
| | ON A11 AND A12. |
| | |
| | 4) THE CITY OF WPB AMENDMENTS TO THE |
| | 2001 FBC 1804.1.7 REQUIRES THE FLOOR |
| | ELEVATION OF A MONOLITHIC SLAB AT |
| | HABITABLE AREAS TO BE 4" ABOVE FINISH |
| | GRADE AT THE BUILDING PERIMETER. |
| | |
| | 5) FBC 2504.2.1 AND ASTM C 926 REQUIRES |
| | EXTERIOR PORTLAND BASED CEMENT PLASTER |
| | (STUCCO) TO BE 5/8" THICH WHEN APPLIED |
| | VERTICALLY OVER METAL LATH AND 7/8" |
| | THICK WHEN APPLIED HORIZONTALLY ON |
| | METAL |
| | LATH OVER SOLID BASE. REVISE PLANS. |
| | |
| | 6) PLEASE CLARIFY THE 4X4 WOOD POST |
| | (WP-1 ON S1). NOTE 7 UNDER THE |
| | FOUNDATION PLAN SPECIFIES A SIMPSON |
| | ABU 44 POST BASE AND DOESN'T SPECIFY |
| | THE |
| | FASTENERS. THE MASONRY PIER DETAIL HAS |
| | A |
| | SIMPSON EPB 44T BASE, BUT NO ID TAG. |
| | |
| | 7) THE OPEN AREAS ABOVE THE LIVING |
| | ROOMS |
| | ARE NOT REFLECTED ON THE SECOND FLOOR |
| | FRAMING PLANS ON S1. |
| | |
| | 8) THE CITY OF WPB AMENDMENTS TO FBC |
| | TABLE 2306.1 REQUIRES THE ROOF |
| | SHEATHING |
| | TO BE NAILED WITH 8DS AT 6"OC AT EDGES |
| | AND 6"OC INTERMEDIATE IN ZONES 1 AND 2 |
| | & WITH 8D RING SHANKS AT 4" OC AT EDGES |
| | AND 6"OC INTERMEDIATE IN ZONE 3. REVISE |
| | SCHEDULE ON S3. THE DIAGRAM DOES NOT |
| | INDICATE ZONES FOR A GABLE ROOF. |
| | |
| | 9) TRUSS LAYOUT AND DRAWINGS ARE |
| | REQUIRED TO HAVE THE WET SIGNATURE OF |
| | THE TRUSS ENGINEER PER FAC |
| | 61G15-23.002. |
| | |
| | 10) TRUSS DRAWINGS DO NOT REFLECT THE |
| | OPEN AREAS ABOVE THE LIVING ROOMS OF THE |
| | TWO STORY UNITS SHOWN ON THE FLOOR |
| | PLANS. |
| | |
| | 11) REVISE THE TRUSS LAYOUTS TO MATCH |
| | THE "B" ELEVATION COLUMNS AND OTHER |
| | COMMENTS NOTED BY THE DESIGNER OF |
| | RECORD. |
| | |
| | 12) THE MG1 GIRDER AT THE REAR GABLE ON |
| | THE TRUSS LAYOUT IS NOT INDICATED ON THE |
| | ARCH.PLANS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |