Plan Review Notes
Plan Review Notes For Permit 04110518
Permit Number 04110518
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-19 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SEE MISSING REQUIRED
 LICENSE INFORMATION ON TITLE BLOCK PER
 FAC 61G15-23.002 , AS REQUIRED UNDER FS
 471.023
  
 2)NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR TO BE SIZED PER 250.66
 IF SEC'S FROM FPL CAN NOT BE VERIFIED BY
 FPL, PLEASE PROVIDE NOTE FOR SIZING
 PER 250.66
 THE #2 SHOWN APPEARS TO BE TO SMALL FOR
 600A METER CENTER.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]