Plan Review Notes
Plan Review Notes For Permit 04110518
Permit Number 04110518
Review Stop B
Sequence Number 1
Notes
Date Text
2004-12-15 00:00:00DENIED
  
 1) THE THICKNESS OF THE STUCCO FINISH
 OVER THE METAL LATH ON THE SOFFITS IS
 INCORRECTLY SPECIFIED AS 1/2" THICK. FBC
 2504.2.1 AND ASTM C 926 REQUIRES IT TO
 BE 5/8" APPLIED HORIZONTALLY AND 7/8"
 WHEN APPLIED VERTICALLY OVER METAL
 LATH.
  
 2) THE ENERGY CALCS. LIST R-19
 INSULATION IN THE CEILINGS AND THE PLANS
 SPECIFY R-30.
  
 3) THE 2X6 WOOD FRAME EXTERIOR WALLS
 WITH R-19 INSULATION SPECIFIED ON THE
 PLANS ARE NOT INDICATED ON THE ENERGY
 CALCS.
  
 4) ON SHEET S3 A SECTION THROUGH THE
 TENANT SEPARATION WALL OF UNITS 3 L AND
 R IS INCORRECTLY IDENTIFIED AS 8 ON S6.
  
 5) THE LOCATION OF THE COLUMNS ON SHEET
 A9 DOES NOT MATCH THOSE ON S2.
  
 6) SHEET S2 SHOWS HIP ROOFS OVER THE
 COVERED ENTRIES AT THE LEFT AND RIGHT
 SIDES. THE ELEVATIONS AND TRUSS LAYOUT
 INDICATE GABLE ROOFS.
  
 7) THE TRUSS LAYOUTS AND DRAWINGS ARE
 REQUIRED TO HAVE THE ORIGINAL WET
 SIGNATURE OF THE TRUSS ENGINEER PER FAC
 61G15-23.002.
  
 8) MAKE CORRECTIONS TO TRUSS LAYOUTS AS
 NOTED BY THE DESIGNER OF RECORD.
  
 9) THE GR01 AND GRO4 TRUSSES FOR THE
 UPPER ROOF DO NOT HAVE CONNECTORS
 SPECIFIED IN THE SCHEDULE THAT ARE
 ADEQUATE TO RESIST THE UPLIFTS SPECIFIED
 IN THE TRUSS DRAWINGS. PLEASE REVIEW
 TRUSS CONNECTOR SCHEDULE FOR REQUIRED
 RESISTANCES.
  
 10) SUBMIT THE UL TEST REPORT FOR THE
 GAF SHINGLES.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714