Plan Review Notes
Plan Review Notes For Permit 04110479
Permit Number 04110479
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-17 00:00:00******** UNSAT ********
  
 1)NOTE: PLANS APPEAR TO BE ADDING A SPA
 TO THE SIDE OF AN EXISTING POOL.
 THERE DOES NOT APPEAR TO BE ANY NEW
 ELECTRICAL EQUIPMENT BEING ADDED OR
 INSTALLED?
 IF ANY NEW ELECTRICAL EQUIPMENT IS BEING
 ADDED, PLEASE ONLY SHOW WHAT IS NEW AND
 IDENTIFY ALL EXSITING. ONLY THE
 HEAT-PUMP IS BEING SHOWN AS EXSITING AT
 THIS TIME.
  
 2)AN ELECTRICAL CONTRACTOR IS SIGNED ON
 FOR AN ELECTRICAL PERMIT, THEREFORE IT
 IS ASSUMED SOME SORT OF NEW ELECTRICAL
 WORK IS BEING DONE.
 IF ALL SHOWN IS NEW:
 PLEASE SUBMIT LOAD CALCUALTIONS FOR NEW
 ADDED LOADS. PLEASE SUBMIT INFORMATION
 FOR NEW SUB-PANEL SHOWN . CONDUIT,
 CONDUCTORS, OCP ETC.
 SHOW SIZE OF EXSITING SERVICE ETC.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]