| Plan Review Notes For Permit 04110479 |
| Permit Number |
04110479 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-17 00:00:00 | ******** UNSAT ******** | | | | | | 1)NOTE: PLANS APPEAR TO BE ADDING A SPA | | | TO THE SIDE OF AN EXISTING POOL. | | | THERE DOES NOT APPEAR TO BE ANY NEW | | | ELECTRICAL EQUIPMENT BEING ADDED OR | | | INSTALLED? | | | IF ANY NEW ELECTRICAL EQUIPMENT IS BEING | | | ADDED, PLEASE ONLY SHOW WHAT IS NEW AND | | | IDENTIFY ALL EXSITING. ONLY THE | | | HEAT-PUMP IS BEING SHOWN AS EXSITING AT | | | THIS TIME. | | | | | | 2)AN ELECTRICAL CONTRACTOR IS SIGNED ON | | | FOR AN ELECTRICAL PERMIT, THEREFORE IT | | | IS ASSUMED SOME SORT OF NEW ELECTRICAL | | | WORK IS BEING DONE. | | | IF ALL SHOWN IS NEW: | | | PLEASE SUBMIT LOAD CALCUALTIONS FOR NEW | | | ADDED LOADS. PLEASE SUBMIT INFORMATION | | | FOR NEW SUB-PANEL SHOWN . CONDUIT, | | | CONDUCTORS, OCP ETC. | | | SHOW SIZE OF EXSITING SERVICE ETC. | | | 215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|