| Plan Review Notes For Permit 04110390 |
| Permit Number |
04110390 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | | | | 1) SHT A4 SANITARY RISER DIAGRAM AT THE | | | WASH MACHINE/LAUNDRY SINK DOES NOT MEET | | | CODE REQUIREMENTS. | | | A) A STANDPIPE IS REQUIRED PER SECTION | | | 1002.1 | | | B) THE CLEANOUT SHALL BE LOCATED 4 FEET | | | ABOVE THE FLOOR FOR ACCESS SECTION | | | 708.10 | | | C) DOUBLE SANITARY TEE PATTERNS SHALL | | | NOT RECEIVE THE DISCHARGE OF APPLIANCES | | | WITH PUMPING ACTION DISCHARGE. SECTION | | | 706.3 | | | | | | 2) ARCHITECT'S SIGNATURE IS A COPY ON | | | ALL SHEETS. COPIES OF SIGNATURES IS NOT | | | APPROVED. FAC 61G1-16.004(5) & FS | | | 481.221 | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|