| Plan Review Notes For Permit 04110388 |
| Permit Number |
04110388 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-08-26 00:00:00 | ************ UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE ONLY ONE SET OF | | | ELECTRICAL REVISED SHEETS WERE | | | SUBMITTED. | | | | | | 2)NOTE: PLEASE SEE REDLINED SD LOCATION | | | IN MASTER BEDRM FROM PREVIOUS REVIEW NOT | | | CORRECTED. | | | PLEASE MOVE SD INOT MASTER BEDRM AREA. | | | SD'S ARE TO BE LOCATED WITHIN 3' OF ANY | | | PEAK ON A SLOPED CEILING AND 12" FROM A | | | FLAT CEILING. | | | NFPA-72 CHAPTER 2 | | | | | | 3)NOTE: PLEASE SEE PLANS SUBMITTED AS A | | | "SUBMITTAL". REVISION FEES ARE OWED. | | | | | | 4 )NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|