2005-08-26 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SEE ONLY ONE SET OF
 ELECTRICAL REVISED SHEETS WERE
 SUBMITTED.
  
 2)NOTE: PLEASE SEE REDLINED SD LOCATION
 IN MASTER BEDRM FROM PREVIOUS REVIEW NOT
 CORRECTED.
 PLEASE MOVE SD INOT MASTER BEDRM AREA.
 SD'S ARE TO BE LOCATED WITHIN 3' OF ANY
 PEAK ON A SLOPED CEILING AND 12" FROM A
 FLAT CEILING.
 NFPA-72 CHAPTER 2
  
 3)NOTE: PLEASE SEE PLANS SUBMITTED AS A
 "SUBMITTAL". REVISION FEES ARE OWED.
  
 4 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]