| Date |
Text |
| 2004-12-06 00:00:00 | BUILDING REVIEW PROVISO: | | | 1-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL | | | FOR 2X STRUCTURAL MULLION AS SPECIFIED | | | ON ARCHITECTURAL PLANS. | | | | | | 2-PROVIDE PRODUCT APPROVAL FOR MISSILE | | | IMPACT ENTRY DOORS AS SPECIFIED ON | | | ARCHITECTURAL PLANS. | | | | | | 3-A) REVISE ENTRY COLUMN DETAIL TO SHOW | | | WHERE ARE 2X12'S BEAMS RESTING ON. | | | B) PROVIDE DETAIL SHOWIN HOW ARE 2X12'S | | | ENTRY PORCH BEAMS RESTING ON THE | | | MASONRY | | | SIDE. SECTION 104.2.1.2 CITY AMENDMENTS | | | TO FBC 2001. | | | | | | 4-PROVIDE ENTRY PORCH DETAILS THAT MATCH | | | ACTUAL CONDITIONS SHOWN ON ROOF FRAMING | | | PLANS. SEE ROOF FRAMING PLAN, COMPARE TO | | | DETAILSC1 AND C2 ON SHEET A6 SUBMITTED | | | AND REVISE THEM AS REQUIRED. SEC. | | | 104.2.1.2 CITY AMENDMENTS | | | | | | 5-SHEET A-3: A) REVISE ROOF LOADS CHART | | | TO INCLUDE THE ATTIC LIVE LOAD REQUIRED | | | BY TABLE 1604.1 FBC 2001 | | | B)REVISE ROOF SHEATHING NOTE. SEE FIGURE | | | 1606.2(C) FBC 2001 FOR CORRECT ZONE 3. | | | |
|