| Plan Review Notes For Permit 04110381 |
| Permit Number |
04110381 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-06-07 00:00:00 | ****** UNSAT ******* | | | | | | 1)NOTE: PLEASE SEE 424.3B FOR MIN OCP OF | | | AHU HEAT. | | | PLEASE ALSO SEE 60A OCP FOR 7.5KW. | | | MIN 125% | | | | | | 2)NOTE: PLEASE SEE RISER, PLEASE SEE | | | MISSING EQUIPMENT GROUNDING CONDUCTOR | | | FROM PANEL"A" TO POOL SUB PANEL. | | | PLEASE ALSO SEE RISER IS MISSING | | | REQUIRED NEUTRAL FOR SAME PANEL. | | | 250.24,250.110,250.122 ETC. | | | | | | 3)NOTE: PLEASE SEE MANY ITEMS ARE SHOWN | | | AS OPTIONAL ON PLANS. PLANS NEED TO | | | REFLECT ACTUAL INSTALLATION OF PROJECT. | | | ROUGH INSPECTIONS HAVE ALREADY BEEN | | | PASSED. | | | PLEASE SEE ORIGINAL PLANS WERE STAMPED | | | "ALL REVSIONS AND OPTIONS ARE TO BE | | | SUBMITTED AND REVIEWED BEFORE ROUGH | | | INSPECTION" | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|