Plan Review Notes
Plan Review Notes For Permit 04110363
Permit Number 04110363
Review Stop B
Sequence Number 1
Notes
Date Text
2004-11-08 00:00:00BUILDING PLAN REVIIEW: FAILED
  
  
 1. PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 NEED FLORIDA PRODUCT APPROVALS OR SITE
 SPECIFIC/LOCAL PRODUCT APPROVAL FOR THE
 TRACO WINDOWS AND SAFEGUARD STORM
 PANELS.
  
  
 ANY QUESTIONS PLEASE CALL
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713