| Plan Review Notes For Permit 04110346 |
| Permit Number |
04110346 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-02-11 00:00:00 | PROVISO: | | | THE GENERATOR EXHAUST SHALL TERMINATE IN | | | SUCH A MANNER THAT TOXIC FUMES CANNOT | | | REENTER A BUILDING OR STRUCTURE THROUGH | | | DOORS, WINDOWS, AIR INTAKES OR THE | | | ENGINE AIR INTAKE SYSTEM.NFPA 110 | | | SECTION 7.10.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|