Plan Review Notes
Plan Review Notes For Permit 04110346
Permit Number 04110346
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2005-03-10 00:00:001. WHEN THE REQUIRED EXISTING FIRE
 PUMP IS REMOVED, AN APPROVED FIRE
 WATCH WILL BE REQUIRED FOR THE
 BUILDING. PROPER NOTIFICATION IS TO
 OCCUR WHEN THE FIRE PUMP IS TAKEN
 OFF-LINE OR REMOVED FROM THE
 BUILDING.
  
 2. EMERGENCY GENERATOR INSTALLATION
 TO COMPLY WITH NFPA 110.
  
 3. THE EXHAUST FROM THE GENERATOR
 SHALL NOT RE-ENTER THE BUILDING. NO
 BACK FEEDING OF VAPORS ARE TO OCCUR.
  
 4. NEW DAY TANK IS TO BE PROPERLY
 LABELED WITH STICKERS INDICATING
 THE PRODUCT NAME, NO SMOKING, ETC.
  
 5. THE NEW FIRE PUMP WHEN INSTALLED
 SHALL BE INSPECTED, TESTED, AND
 APPROVED BY THE FIRE PREVENTION
 BUREAU TO ENSURE PROPER OPERATION.
  
 6. FIRE PUMP INSTALLATION TO COMPLY
 WITH NFPA 20.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910.