Plan Review Notes
Plan Review Notes For Permit 04110346
Permit Number 04110346
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-29 00:00:00******* UNSAT ********
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 MISSING LICENSE INFORMATION REQUIRED ON
 TITLE BLOCKS. PLEASE SEE FS 471.023 FOR
 REQUIRED CA #.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWERS. MECH/FIRE
 STAMPS HAVE BEEN VOIDED.
 PLEASE PROVIDE NEW SHEETS FOR TRADES.
  
 2)NOTE: PLEASE PROVIDE COPY OF
 COMPPLETE
 CONTRACT FOR SCOPE OF WORK. VALUE IS TO
 BE BASED ON LABOR AND MATERIALS. THIS
 WOULD INCLUDE GEN ETC. EVEN IF OWNER
 SUPPLIED. FBC 104.6.5.
 VALUE SHOWN AT $155K.
 IF VALUE SHOWN ON ELECTRICAL PERMIT
 APPLICATION IS TO BE ADDED TO MECH
 PERMIT APPLICATION , PLEASE ADJUST MECH
 PERMIT APPLICATION.
  
 3)NOTE: PLEASE ALSO SUBMIT MANUFACT.
 SPECS ON NEW TRANSFER SWITCH.
  
 4)NOTE: PLEASE SEE # OF CONDUCTORS FROM
 ATS -2 TO NEW DISC(CODED NOTES #10).
 SHOWN AS 3-POLE DISC'S AND EQUIPMENT,
 HOWEVER ONLY 3- CONDUCTORS ARE SHOWN.
 PLEASE SEE 240.4C, 240.21 FOR SIZING OF
 CONDUCTORS AND TERMINATION INTO 400A
 DISC FROM 1000A OCP.
 PLEASE VERIFY THE ABOVE.
  
 5)NOTE: PLEASE VERIFY GFI PROTECTION ON
 GENERATOR PER 240.13,230.95.
 EXISTING EM MAIN, DOES INDICATE GFI
 PROTECTION.
  
 6)NOTE: PLEASE VERIFY , RISER INDICATES
 NEW TRANSFER SWITCH (FORMERLY FIRE
 PUMP)? IS FIRE PUMP FEED BEING REMOVED?
 IS THERE ALREADY A NEW FEED FOR FIRE
 PUMP?
 PLEASE VERIFY.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  