| Date |
Text |
| 2004-11-29 00:00:00 | ******* UNSAT ******** |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR |
| | MISSING LICENSE INFORMATION REQUIRED ON |
| | TITLE BLOCKS. PLEASE SEE FS 471.023 FOR |
| | REQUIRED CA #. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR |
| | ALL TRADES WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWERS. MECH/FIRE |
| | STAMPS HAVE BEEN VOIDED. |
| | PLEASE PROVIDE NEW SHEETS FOR TRADES. |
| | |
| | 2)NOTE: PLEASE PROVIDE COPY OF |
| | COMPPLETE |
| | CONTRACT FOR SCOPE OF WORK. VALUE IS TO |
| | BE BASED ON LABOR AND MATERIALS. THIS |
| | WOULD INCLUDE GEN ETC. EVEN IF OWNER |
| | SUPPLIED. FBC 104.6.5. |
| | VALUE SHOWN AT $155K. |
| | IF VALUE SHOWN ON ELECTRICAL PERMIT |
| | APPLICATION IS TO BE ADDED TO MECH |
| | PERMIT APPLICATION , PLEASE ADJUST MECH |
| | PERMIT APPLICATION. |
| | |
| | 3)NOTE: PLEASE ALSO SUBMIT MANUFACT. |
| | SPECS ON NEW TRANSFER SWITCH. |
| | |
| | 4)NOTE: PLEASE SEE # OF CONDUCTORS FROM |
| | ATS -2 TO NEW DISC(CODED NOTES #10). |
| | SHOWN AS 3-POLE DISC'S AND EQUIPMENT, |
| | HOWEVER ONLY 3- CONDUCTORS ARE SHOWN. |
| | PLEASE SEE 240.4C, 240.21 FOR SIZING OF |
| | CONDUCTORS AND TERMINATION INTO 400A |
| | DISC FROM 1000A OCP. |
| | PLEASE VERIFY THE ABOVE. |
| | |
| | 5)NOTE: PLEASE VERIFY GFI PROTECTION ON |
| | GENERATOR PER 240.13,230.95. |
| | EXISTING EM MAIN, DOES INDICATE GFI |
| | PROTECTION. |
| | |
| | 6)NOTE: PLEASE VERIFY , RISER INDICATES |
| | NEW TRANSFER SWITCH (FORMERLY FIRE |
| | PUMP)? IS FIRE PUMP FEED BEING REMOVED? |
| | IS THERE ALREADY A NEW FEED FOR FIRE |
| | PUMP? |
| | PLEASE VERIFY. |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |