| 2004-12-28 00:00:00 | *** UNSAT *** |
| | |
| | 1)NOTE: PLEASE SEE ELECTRICAL PLANS ARE |
| | NOW COMING BACK IN SEALED BY THE |
| | ENGINEER, HOWEVER, STAMP FROM ENGINEER |
| | IS FOR STRUCTURE ONLY. |
| | ENGINEERS TITLE BLOCK IS NOT COMPLETE |
| | PER FAC 61G15-23.002 FOR OTHER SHEETS |
| | ALSO. |
| | |
| | **PLEASE UNDERSTAND ELECTRICAL PLANS FOR |
| | A SF RESIDENCEARE NOT REQUIRED TO BE |
| | SIGNED AND SEALED BY AN ARCH OR |
| | ENGINEER, HOWEVER FBC 104.2.1 DOES |
| | REQUIRE THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR PLANS. |
| | IF THE ENGINEER AS STAMPED ON PLANS IS |
| | FOR STRUCTUAL, THEN HE IS NOT PERMITTED |
| | TO SIGN AND SEAL ELECTRICAL PLANS IF NOT |
| | DONE BY HIM. |
| | PLEASE CALL IF THERE ARE ANY QUESTIONS, |
| | ABOUT THIS. |
| | |
| | 3)NOTE: PLEASE SEE ONE SET OF PLANS HAS |
| | THE REDLINE DMISSING RECEPTS IN LIVING |
| | RM PER 210.52 |
| | |
| | 4)NOTE: PLEASE SEE NOTE ON LOWER |
| | RIGHT-HAND SIDE OF PLANS MENTIONS ARC |
| | FAULT FOR RECEPTS AND ARC FAULT RECEPTS |
| | TO BE INSTALLED. PLEASE SEE ARC FAULT |
| | RECEPTS ARE NOT AVAILABLE AND ARE NOT |
| | MADE AT THIS TIME. |
| | SINCE PLANS ARE COMING BACK, PLEASE |
| | REMOVE NOTE: |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |