| Date |
Text |
| 2004-11-12 00:00:00 | ********** UNSAT ************* |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | |
| | 2) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | PLEASE ALSO SEE BOTH BATHS NOT SHOWING |
| | ANY ELECTRICAL ?? |
| | |
| | 3)NOTE: PLEASE SEE BOTH BATHS ? 210.70 |
| | |
| | |
| | 4)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 2002 NEC 210.12 |
| | |
| | 5)NOTE: PLEASE SEE LIVING RM RECEPT |
| | SPACING. 210.52 |
| | |
| | 6)NOTE: PLEASE SEE FBC 104.2.1, PLANS |
| | ARE REQUIRED TO HAVE PRINTED NAME AND |
| | SIGNATURE OF PERSON RESPONSIBLE FOR |
| | PLANS. |
| | PLEASE ALSO SEE TITLE BLOCK AND MISSING |
| | INFORMATION PER FAC 61G1-16.004, FS |
| | 481.219. |
| | ARCH FIRM? FS 481.221 |
| | ENG FIRM? FS 471.025,471.023, |
| | 61G15-23.002 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDEDSHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |