| 2004-12-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) PER TABLE 403.1 A DRINKING FOUNTAIN |
| | IS REQUIRED IN EACH SPACE. ALSO SEE |
| | SECTION 410.1. |
| | 2) INDICATE THE OCCUPANCY OF EACH UNIT. |
| | SECTION 104.2.1 |
| | 3) DETAIL FOR ACCESSIBLE TOILET ROOM AND |
| | ACCESSIBLE FIXTURES IS MISSING THE |
| | FOLLOWING INFORMATION. |
| | A) 11-4.16.2 CLEAR FLOOR SPACE FOR THE |
| | WATER CLOSET. |
| | B) 11-4.16.3 HEIGHT OF THE W/C |
| | C) 11-4.16.5 FLUSH CONTROLS |
| | D) 11-4.19.3 CLEAR FLOOR SPACE WITH |
| | FORWARD APPROACH. SEE FIG.32. |
| | 4) APPLICATION INDICATES EXTERIOR WINDOW |
| | REPLACEMENT AS THE "DESCRIPTION OF |
| | PROJECT IN DETAIL" IT APPEARS THAT MORE |
| | WORK THAN DESCRIBED WILL BE DONE. PLEASE |
| | SHOW ON THE APPLICATION ALL WORK IN |
| | DETAIL. ALSO THE VALUATION OF THE WORK |
| | WILL BE CALCULATED FOR ALL WORK. |
| | SECTIONS 104.1..1 AND 104.6.5 |
| | 6) SUBMIT A BUILDING DRAIN ISOMETRIC |
| | SHOWING THE POINT OF CONNECTION FOR EACH |
| | TOILET ROOM. SHOW ALL PIPE SIZING. |
| | SECTION 104.3.1.1 |
| | 7) SUBMIT A WATER RISER DIAGRAM SHOWING |
| | ALL POINTS OF CONNECTION AND VALVES |
| | REQUIRED BY SECTION 606.1(4) IF OVERHEAD |
| | WATER PIPING. SECTION 104.3.1.1 |
| | 8) THE FOLLOWING INFORMATIONS IN |
| | REQUIRED ON THE TITLE BLOCK OF THE |
| | ARCHITECT OF RECORD. THE FIRM LICENSE |
| | NUMBER. 61G1-16.004(2) & FS 481.2055 |
| | |
| | |
| | |
| | REVIEW BY KEN STEVENS |