| Plan Review Notes For Permit 04110265 |
| Permit Number |
04110265 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-04 00:00:00 | DENIED: | | | 1.PLAN SHEET 3.1 & 8.1 INDICATE THE | | | SEPARATION BETWEEN THE WAREHOUSE AND THE | | | OFFICE AREA HAS A 2 HR FIRE RATING. | | | PLEASE PROVIDE LOCATION AND DETAIL OF | | | FIRE DAMPER AS REQUIRED PER 2001 FBC(M) | | | 607.1.2 & 607.6. | | | | | | 2.PLAN DOES NOT INDICATE CONDENSATE | | | TERMINATION, SHOW COMPLIANCE WITH 2001 | | | FBC(M) 307.2.1 & FBC 1503.4.4. | | | | | | 3.DETAIL OF CONDENSING UNIT SUPPORT ON | | | PLAN SHEET 7.1, CLEARANCE BETWEEN THE | | | ROOF SURFACE AND THE BOTTOM OF THE | | | SUPPORT RAIL SHALL COMPLY WITH 2001 FBC | | | 1511.7. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|