| Plan Review Notes For Permit 04110262 |
| Permit Number |
04110262 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-12 00:00:00 | *********** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE 210.52C1 FOR MISSING | | | GFI ALONG KITCHEN COUNTERSPACE. | | | | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 3)NOTE: PLEASE SEE GARAGE IS SHOWN ON A | | | 1P30A CIRCUIT W/ #12 AWG? | | | 240.4 | | | | | | PLEASE SEE ZONING COMMENTS ON PLANS. | | | | | | PLEASE REMOVE ALL/OLD VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|