2004-12-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110234
 ADD: 1019 WINDSOR AV
 CONT: INTEGRITY BUILDING CONT
 TEL: (561)841-1666
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN
 QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE
 EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL
 J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
 4) SHEET A.1 NOTES LISTED UNDER PLYWOOD
  
 ROOF SHEATHING, (D) HIGH RIB LATH
 NAILINGSHALL COMPLY WITH, 2504.2.2.
 2504.2.2 INSTALLATION OF EXTERIOR
 LATHING AND FRAMING SHALL COMPLY WITH
 ASTM C-1063.(7.10.2.3) EXPANDED 3/8"
 RIB
 LATH SHALL BE ATTACHED TO HORIZONTAL
 FRAMING MEMBERS WITH NAILS OR STAPLES
 TO
 PROVIDE AT LEAST 1 3/4" PENETRATION
 INTO
 THE WOOD FRAMING MEMBER, 3/4" INTO
 VERTICAL WOOD FRAMING MEMBERS.
 7.10.1.1RIB LATH SHALL BE ATTACHED
 TO FRAMINGMEMBERS AT EACH RIB
 (4") O.C.5)
  
 5) SHEET A.1 WOOD NOTES INDICATE THAT
 THE WOOD TRUSSES ARE TO BE REVIEWED BY
 THE DESIGNER OF RECORD BEFORE
 FABRICATION. THIS ALSO HOLD TRUE FOR
 THE
 BUILDING DEPARTMENT, PLEASE HAVE THE
 DESIGNER OF RECORD REVIEW AND DOCUMENT
 BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT.
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FRENCH DOORS IF REPORT JELD-WEN IS
 TO BE USED , HIGHLIGHT THE PRODUCT AND
 MODEL DESCRIPTION, TO IDENTIFY THE
 LIMITS OF USE.
  
 7) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, THE
 STORM SHUTTER REPORT SUBMITTED,
 HIGHLIGHT THE CONNECTION TYPES TO BE
 USED. ALSO HIGHLIGHT THE ANCHORS TO BE
 USED, AND THE TYPE OF STRUCTURE, USE
 **CONCRETE**.
  
 8) SHEET A.3 TRUSS ANCHOR SCHEDULE,
 SCHEDULE INDICATE THE USE OF SIMPSON &
 USP BUT THE SCHEDULE DOESN'T INDICATE
 IF THE REFRENCEED STOCK NUMBER IS USP OR
  
 SIMPSON, SOME ARE BOTH WITH DIFFERENT
 VALUES.
 1707.3.1 JOIST HANGERS, FRAMING ANCHORS
 & SIMILAR DEVICES SHALL BE TEST- ED IN
 ACCORDANCE W/ ASTM D 1761 & BE LABELED
 AND LISTED FOR THEIR LOAD CARRY- ING
 CAPACITY.
 UNTIL THE MANUFACTURER IS KNOWN THE
 VALUES WILL NOT BE REVIEWED, REMEMBER:
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
  
 9)1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 10) ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 11) SEE THE ATTACHED SHEET FOR REQUIRE-
 MENTS FOR ROYAL WALL PRODUCTS.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) CALCULATED VALUE:
 A/C AREA 1224 SQ FT X $76.96=$94,199.04
 NON AREA91 SQ FT X $41.60=$ 3,785.60
 TOT AREA 1315 SQ FTTOTAL$97,984.64
  
  
 BUILDING PLAN REVIEW
 JIM WITMER